Review Type |
Outcome |
Est. Completion Date |
Completed |
Building Review
|
Failed
|
10/28/2024
|
10/23/2024
|
|
|
|
Other/Miscellaneous
B-1) Please see engineering comments.
B-2) It looks like four retaining walls are identified as needing separate permits.
B-3) Please seal plan set. (Struct Plan)
B-4) Please provide construction details for vehicle barriers.
|
|
Other/Miscellaneous
Please revise the application form to correctly specify which wall is associated with this permit.
|
|
|
Planning Review
|
Failed
|
10/28/2024
|
10/23/2024
|
|
|
|
Miscellaneous Planning Correction
Comment Outstanding: 10/23/24 - Submittal 2
Include grading plan in submittal.
|
|
Other/Miscellaneous
Updated comment: 10/23/24 - Submittal 2
Updated plan sheets now highlight that this application is for the northwest retaining wall. Resubmit an updated application form that states this retaining wall application is for the northwest retaining wall instead of for the southern boundary as it currently states.
Clarify on plan set which retaining walls is being applied for as application form states the application for the retaining wall is along the southern boundary, but paving schedule calls out #20 - "lock 7 load" landscape retaining wall that is located along the eastern property line - plans are unclear.
|
|
See Document Markup
Site plan should match civil plan. This is required to be a wall and no a security fence. The previous submittal noted this correctly, but appears to be updated and is now incorrect. Previously was identified as Paving Plan Schedule #15. [site plan, C4]
|
|
|
Building Review
|
Failed
|
04/04/2024
|
04/03/2024
|
|
|
|
Other/Miscellaneous
B-1) Please see engineering comments.
B-2) It looks like four retaining walls are identified as needing separate permits.
B-3) Please seal plan set. (Struct Plan)
B-4) Please provide construction details for vehicle barriers.
|
|
|
Engineering Review
|
Failed
|
04/04/2024
|
04/03/2024
|
|
|
|
Other/Miscellaneous
There is a discrepancy between the permit application description, site plan, and structural calculations as to which wall to review. The permit application refers to the wall along the southern property line, the site plan indicates that the lock and load wall is along the eastern property line, and the structural calculations refer to the wall along the northwest property line. Please resolve the discrepancy and submit a site plan that clearly indicates the wall in question. All other retaining walls depicted on the site plan shall be permitted separately. Please note, any retaining wall 4-feet or taller requires a City of Puyallup building permit. Walls shorter than 4-feet must comply with City standard details section 05.03. [Yianni Charitou @ 04/03/2024 10:24 AM]
|
|
|
Planning Review
|
Failed
|
04/04/2024
|
03/28/2024
|
|
|
|
Miscellaneous Planning Correction
Include grading plan in submittal.
|
|
Other/Miscellaneous
Clarify on plan set which retaining walls is being applied for as application form states the application for the retaining wall is along the southern boundary, but paving schedule calls out #20 - "lock 7 load" landscape retaining wall that is located along the eastern property line - plans are unclear.
|
|
|
Engineering Civil Review
|
Failed
|
04/04/2024
|
03/27/2024
|
|
|
|
See Document Markup
Make a note on all sheets that wall drainage connections are shown on civil permit PRCCP20231096 and is to be connected to the private storm system. [site plan, pg 1]
|
|
See Document Markup
Provide wall details on the plan set. [site plan, pg 1]
|
|
See Document Markup
Revise wall language, for clarity. This plan states to see separate plans (what separate plans?) and this building permit. Ensure these building plan sheets match the civil plan callouts and details. [site plan, pg 1]
|
|
|
Engineering Review
|
Pending
|
10/28/2024
|
|
|
|
|
If the PRCCP20231096 Engineering Civil review is approved this round (due 11/01/2024), Engineering can resolve comment correction and approve. Otherwise, fail with outstanding correction below until civil has been approved and the plans match. [Yianni Charitou @ 10/22/2024 1:19 PM]
|
Engineering Civil Review
|
Pending
|
10/28/2024
|
|
|
|
|
CityView system: 10/14/2024 8:39 AM - Activity assignment changed from 'Anthony Hulse' to 'Sam Morman' due to employee availability configuration.
|