Summary

PRCA20220580
Commercial - Addition
Closed
CASCADE CHRISTIAN SCHOOLS
Addition
Minor interior TI & Adding 1771 SF to the existing office building REVISION (1) - 2/23/2023 - MECHANICAL DESIGN ADJUSTMENT
03/30/2022
11/07/2022
04/23/2024
10/26/2023

Locations

Reviews

Documents Returned For Corrections

Review Type Outcome Est. Completion Date Completed
Building Review Approved 03/16/2023 03/03/2023
Fire Review Approved 03/16/2023 02/23/2023
Planning Review VOID 03/16/2023 02/23/2023
Engineering Traffic Review VOID 03/16/2023 02/23/2023
Engineering Review VOID 03/16/2023 02/23/2023
Engineering Traffic Review Approved 10/29/2022 10/31/2022
Fire Review Approved 10/29/2022 10/25/2022
Planning Review Approved 10/29/2022 10/24/2022
Engineering Review Approved 10/29/2022 10/17/2022
Building Review Approved 10/29/2022 10/14/2022
Engineering Traffic Review Approved 05/01/2022 05/24/2022
Engineering Review Approved 05/01/2022 05/17/2022
Building Review Failed 05/01/2022 05/11/2022
Fire Review Approved 05/01/2022 05/09/2022
Planning Review Approved 05/01/2022 04/11/2022

Fees

Paid Fees Amount Paid Owing Date Paid
Fire Review Fee (Commercial Building) $265.00 $265.00 Paid 11/04/2022
Air Handling Unit (Up to 10,000 cfm) Fee $28.20 $28.20 Paid 11/04/2022
Mechanical Duct Work Fee $24.00 $24.00 Paid 11/04/2022
Unclassified Appliance or Equipment Fee $28.20 $28.20 Paid 11/04/2022
Ventilation System (apart from Heating/AC) Fee $28.20 $28.20 Paid 11/04/2022
Building Permit Fee $2,393.75 $2,393.75 Paid 11/04/2022
Mechanical Permit Fee $40.00 $40.00 Paid 11/04/2022
Plumbing Permit Fee $40.00 $40.00 Paid 11/04/2022
Plumbing Fixtures Fee $52.00 $52.00 Paid 11/04/2022
Building Plan Review Fee $1,555.94 $1,555.94 Paid 03/31/2022
Mechanical Plan Review Fee $96.59 $96.59 Paid 03/31/2022
Plumbing Plan Review Fee $59.80 $59.80 Paid 03/31/2022
WA State Building Code Council Fee (Commercial) $25.00 $25.00 Paid 11/04/2022
Sewer System Development Charge Fee - Tenant Improvment/Addition $2,367.78 $2,367.78 Paid 11/04/2022
Water System Development Charge Fee - Tenant Improvment/Addition $1,284.39 $1,284.39 Paid 11/04/2022
Storm System Development Charge - Commercial $3,560.00 $3,560.00 Paid 11/04/2022
Resubmittal/Revision Fee $130.00 $130.00 Paid 08/03/2022
Resubmittal/Revision Fee $130.00 $130.00 Paid 02/27/2023
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Footing/Setback Inspection Not Ready 12/1/2022 12/1/2022 12/01/2022
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Carried Forward
12/01/2022
1 ; provide E&S inspection approval prior to footing inspection. not ready

Erosion And Sediment Inspection Passed w/ Conditions 12/1/2022 12/1/2022 12/01/2022
Jason Little ((253) 244-0387)
Footing/Setback Inspection Not Ready 12/5/2022 12/5/2022 12/05/2022
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Resolved
12/05/2022
1 ; provide E&S inspection approval prior to footing inspection. not ready

Other/Miscellaneous
Carried Forward
12/05/2022
1 ; remove standing water and show from footing prior to inspection. 2 ; did not check setbacks or open City approved plans. not ready

Footing/Setback Inspection Passed 12/6/2022 12/6/2022 12/06/2022
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Resolved
12/06/2022
1 ; remove standing water and show from footing prior to inspection. 2 ; did not check setbacks or open City approved plans. not ready

Foundation/Rebar Inspection Failed 12/9/2022 12/9/2022 12/09/2022
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Carried Forward
12/09/2022
1 ; provide min. bar lap as per City approved plans as discussed with contractor. 2 ; provide special inspection approval prior to foundation inspection. not ready

Foundation/Rebar Inspection Passed w/ Conditions 12/12/2022 12/12/2022 12/12/2022
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Resolved
12/12/2022
1 ; provide min. bar lap as per City approved plans as discussed with contractor. 2 ; provide special inspection approval prior to foundation inspection. not ready

Storm Inspection Failed 12/16/2022 12/16/2022 12/16/2022
Jason Little ((253) 244-0387)
Underfloor Inspection Failed 12/20/2022 12/20/2022 12/20/2022
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Carried Forward
12/20/2022
1 ; provide barrier at hanger in contact with p.t. wood. 2 ; provide barrier at beam in contact with concrete at n.w. corner of building. 3 ; compete anchor bolt at s.e. corner of building.

Underfloor Inspection Passed 12/22/2022 12/22/2022 12/22/2022
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Outstanding
12/20/2022
1 ; provide barrier at hanger in contact with p.t. wood. 2 ; provide barrier at beam in contact with concrete at n.w. corner of building. 3 ; compete anchor bolt at s.e. corner of building.

Storm Inspection Passed 1/6/2023 1/6/2023 01/06/2023
Michael Rosenau ((253) 344-6753)
Shear Wall Inspection Partial Pass 1/17/2023 1/17/2023 01/17/2023
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Carried Forward
01/24/2023
1 ; complete shearwall at grid line - (c-e.3.5-4) ok to cover at grid line -( d-f,4-5)

Shear Wall Inspection Passed 1/24/2023 1/24/2023 01/24/2023
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Outstanding
01/24/2023
1 ; complete shearwall at grid line - (c-e.3.5-4) ok to cover at grid line -( d-f,4-5)

Mechanical Rough In Inspection Not Ready 2/23/2023 2/23/2023 02/23/2023
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Carried Forward
02/23/2023
1. see correction on framing inspection todays date

Frame Inspection Not Ready 2/23/2023 2/23/2023 02/23/2023
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Carried Forward
02/23/2023
1.complete sole plate nailing per city approved plans 2.strap all beams and plates as discussed with contractor 3.provide energy paper work at time of next inspection 4. provide approved revision for MECH platform at time of next inspection 5.provide blocks at wall where trusses bear as discussed with contractor 6.provide bearing at girder truss Ho3 4 locations 7.provide letter from engineer of record on clarification of detail 4 on page S 1.2 8. plumbing approved 9.not ready

Plumbing Rough In Inspection Passed 2/23/2023 2/23/2023 02/23/2023
Kevin Spruell ((253) 841-5590)
Mechanical Rough In Inspection Not Ready 3/7/2023 3/7/2023 03/07/2023
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Carried Forward
03/07/2023
1. see correction on framing inspection todays date

Other/Miscellaneous
Carried Forward
03/07/2023
1. provide ladder to inspect MECH plat form 2.not ready

Frame Inspection Partial Pass 3/7/2023 3/7/2023 03/07/2023
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Carried Forward
03/07/2023
1.complete sole plate nailing per city approved plans 2.strap all beams and plates as discussed with contractor 3.provide energy paper work at time of next inspection 4. provide approved revision for MECH platform at time of next inspection 5.provide blocks at wall where trusses bear as discussed with contractor 6.provide bearing at girder truss Ho3 4 locations 7.provide letter from engineer of record on clarification of detail 4 on page S 1.2 8. plumbing approved 9.not ready

Other/Miscellaneous
Carried Forward
03/07/2023
1.complete bearing at girder truss as discussed with contractor from previous list 2. OK TO INSULATE

Energy (Insulation) Inspection Passed 3/10/2023 3/10/2023 03/10/2023
Kevin Spruell ((253) 841-5590)
Wallboard / Drywall Inspection Passed 3/16/2023 3/16/2023 03/16/2023
Shannon King ((253) 840-6684)
Comment Building Div Inspection Not Ready 5/1/2023 5/1/2023 05/01/2023
Shannon King ((253) 840-6684)
Planning Final Inspection Passed 5/2/2023 05/02/2023
Chris Beale ((253) 841-5418)
Fire Final Inspection Partial Pass 5/2/2023 5/2/2023 05/02/2023
David Drake ((253) 864-4171)
Corrections:


Other/Miscellaneous
Carried Forward
05/02/2023
Approved for stocking; verified with building inspector 12-27 2022 Elevator not in service: recall not tested

Engineering Final Inspection Not Ready 5/2/2023 5/2/2023 05/02/2023
Jason Little ((253) 244-0387)
Engineering Final Inspection Partial Pass 5/3/2023 05/03/2023
Jason Little ((253) 244-0387)
Building Final Inspection Not Ready 5/4/2023 5/4/2023 05/04/2023
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Carried Forward
05/04/2023
1 ; talked about building, mechanical, final requirements. not ready

Building Final Inspection Not Ready 5/8/2023 5/8/2023 05/08/2023
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Carried Forward
05/08/2023
1 ; talked about building, mechanical, final requirements. not ready

Other/Miscellaneous
Carried Forward
05/08/2023
1 ; cancel per contractor.

Building Final Inspection Partial Pass 5/9/2023 5/9/2023 05/09/2023
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Carried Forward
05/09/2023
1 ; talked about building, mechanical, final requirements. not ready

Other/Miscellaneous
Carried Forward
05/09/2023
1 ; cancel per contractor.

Storm Inspection Partial Pass 5/16/2023 5/16/2023 05/16/2023
Jason Little ((253) 244-0387)
Engineering Final Inspection Not Ready 5/16/2023 05/16/2023
Jason Little ((253) 244-0387)
Building Final Inspection Partial Pass 5/17/2023 5/17/2023 05/17/2023
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Carried Forward
05/17/2023
1 ; talked about building, mechanical, final requirements. not ready

Other/Miscellaneous
Resolved
05/17/2023
1 ; cancel per contractor.

Frame Inspection Not Ready 7/12/2023 7/12/2023 07/12/2023
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Resolved
07/12/2023
1.complete sole plate nailing per city approved plans 2.strap all beams and plates as discussed with contractor 3.provide energy paper work at time of next inspection 4. provide approved revision for MECH platform at time of next inspection 5.provide blocks at wall where trusses bear as discussed with contractor 6.provide bearing at girder truss Ho3 4 locations 7.provide letter from engineer of record on clarification of detail 4 on page S 1.2 8. plumbing approved 9.not ready

Other/Miscellaneous
Resolved
07/12/2023
1.complete bearing at girder truss as discussed with contractor from previous list 2. OK TO INSULATE

Other/Miscellaneous
Carried Forward
07/12/2023
1. this inspection is for phase 2 2.provide poly seal as discussed with contractor 3.provide positive connection at all plate breaks ,wall tie ins and tie in to existing building 4.provide clarification from architect on interior door hts per city approved plans 5.provide electrical cover approval at time of next inspection 6. provide attic access by final 7. plumbing approved

Frame Inspection Failed 7/14/2023 7/14/2023 07/15/2023
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Carried Forward
07/15/2023
1. this inspection is for phase 2 2.provide poly seal as discussed with contractor 3.provide positive connection at all plate breaks ,wall tie ins and tie in to existing building 4.provide clarification from architect on interior door hts per city approved plans 5.provide electrical cover approval at time of next inspection 6. provide attic access by final 7. plumbing approved

Other/Miscellaneous
Carried Forward
07/15/2023
1. complete previous list

Firewall/Firestop Inspection Passed w/ Conditions 7/17/2023 7/17/2023 07/17/2023
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Outstanding
07/17/2023
1 ; complete install of exhaust fan in restroom prior to frame approval.

Comment Building Div Inspection Passed 7/18/2023 7/18/2023 07/18/2023
Shannon King ((253) 840-6684)
Sidesewer Inspection Passed 7/24/2023 7/24/2023 07/24/2023
Jason Little ((253) 244-0387)
Water Service Inspection Failed 7/24/2023 7/25/2023 07/25/2023
Jason Little ((253) 244-0387)
Water Service Inspection Partial Pass 8/1/2023 08/01/2023
Jason Little ((253) 244-0387)
Engineering Final Inspection Passed 9/13/2023 9/12/2023 09/12/2023
Jason Little ((253) 244-0387)
Fire Final Inspection Passed 10/5/2023 10/05/2023
David Drake ((253) 864-4171)
Corrections:


Other/Miscellaneous
Outstanding
05/02/2023
Approved for stocking; verified with building inspector 12-27 2022 Elevator not in service: recall not tested

Emergency Radio Test Review Inspection VOID 10/05/2023
David Drake ((253) 864-4171)
Hydrostatic Test 200Lbs 2Hrs VOID 10/05/2023
David Drake ((253) 864-4171)
Fire Or Smoke Damper Inspection VOID 10/05/2023
David Drake ((253) 864-4171)
Building Final Inspection Not Ready 10/10/2023 10/10/2023 10/10/2023
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Resolved
10/10/2023
1 ; talked about building, mechanical, final requirements. not ready

Other/Miscellaneous
Carried Forward
10/10/2023
FINAL INSPECTION ON ADMIN OFFICE 1. provide exit signage as discussed with contractor 2. provide correct hardware and door signage at required exit doors as discussed with contractor 3. provide insulation at attic access

Building Final Inspection Passed 10/25/2023 10/25/2023 10/26/2023
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Resolved
10/26/2023
FINAL INSPECTION ON ADMIN OFFICE 1. provide exit signage as discussed with contractor 2. provide correct hardware and door signage at required exit doors as discussed with contractor 3. provide insulation at attic access

Comment Engineering Div Inspection VOID 10/26/2023
Kevin Spruell ((253) 841-5590)
Slab/Insulation Inspection VOID 10/26/2023
Kevin Spruell ((253) 841-5590)
Block Wall Rebar Inspection VOID 10/26/2023
Kevin Spruell ((253) 841-5590)
Ceiling Grid/T-Bar Inspection VOID 10/26/2023
Kevin Spruell ((253) 841-5590)
Re-Roof Inspection VOID 10/26/2023
Kevin Spruell ((253) 841-5590)
Gas Test Inspection VOID 10/26/2023
Kevin Spruell ((253) 841-5590)
Refrigeration Line Test Inspection VOID 10/26/2023
Kevin Spruell ((253) 841-5590)
Exhaust/Vent Fans Inspection VOID 10/26/2023
Kevin Spruell ((253) 841-5590)
Cover Inspection/Thrust Blocks Inspection VOID 10/26/2023
Kevin Spruell ((253) 841-5590)
Floodproof Certification Inspection VOID 10/26/2023
Kevin Spruell ((253) 841-5590)
Elevation Verification Inspection VOID 10/26/2023
Kevin Spruell ((253) 841-5590)
Plumbing Final Inspection VOID 10/26/2023
Kevin Spruell ((253) 841-5590)
Mechanical Final Inspection VOID 10/26/2023
Kevin Spruell ((253) 841-5590)
Mechanical Rough In Inspection VOID 10/26/2023
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Outstanding
03/07/2023
1. see correction on framing inspection todays date

Other/Miscellaneous
Outstanding
03/07/2023
1. provide ladder to inspect MECH plat form 2.not ready

Storm Inspection VOID 10/26/2023
Kevin Spruell ((253) 841-5590)
Frame Inspection VOID 10/26/2023
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Outstanding
07/15/2023
1. this inspection is for phase 2 2.provide poly seal as discussed with contractor 3.provide positive connection at all plate breaks ,wall tie ins and tie in to existing building 4.provide clarification from architect on interior door hts per city approved plans 5.provide electrical cover approval at time of next inspection 6. provide attic access by final 7. plumbing approved

Other/Miscellaneous
Outstanding
07/15/2023
1. complete previous list

Water Service Inspection VOID 10/26/2023
Kevin Spruell ((253) 841-5590)

Conditions

Condition Status Category
Building Permit Standard Conditions Open Standard Conditions
* Final approval by the Building Official is required prior to use or occupancy.* Work shall not proceed until the inspector has approved the stages of construction.* Surface storm water shall be diverted from the building site and shall not drain onto adjacent properties.* I hereby acknowledge that I have read this Permit/Application, that the information given is correct; that I am the owner or the duly authorized agent of the owner; that plans submitted herewith are in compliance with all applicable city, county and state laws and that all construction will proceed in accordance with said laws. This permit shall expire if work is not commenced with 180 days or if the work is suspended for a period of 180 days. Permits expire two years from issuance. * By leaving the contractor information section blank, I hereby certify further that contractors (general or subcontractors) will not be hired to perform any work in association with this permit. I also certify that if I do choose to hire a contractor (general or subcontractor) I will only hire those contractors that are licensed by the State of Washington. If you are a property owner, contractor or permittee and you are paying for someone to perform the work, they must have a valid contractor registration and the person(s) installing plumbing inside a structure must meet the plumbing certification requirements. If you have any questions regarding these regulations, you may contact the Washington State Department of Labor and Industries or you can find more information on-line at: http://www.lni.wa.gov/TradesLicensing/Contractors/HireCon/default.asp
Fire Review Conditions Open Standard Conditions
• Comply with 2018 IFC and 2018 IBC • Total coverage required in the city of puyallup • L&I Final required prior to Fire Final • Exit lighting test required contractor to provide light meter • A separate permit may be required if fire alarm or sprinkler system is altered • RTU’S will be required to be tested for shut down. • Fire extinguishers required per code • A Knox box is required at the front entry on the exterior of the building • PIV must have a Knox lock or approved lock with an extra key provided in Knox box • Existing buildings will need to contact central pierce fire & rescue and update the key in the Knox box • All above items to be completed prior to fire final. Fire final required before building final Schedule your inspection online through the City of Puyallup online permit system. This is a request for inspection only. A date and time will be selected by Inspector depending on availability. Email prior to inspection for date and time. Fire Inspections are Monday – Thursday there will be no inspections on Fridays. David Drake 253-864-4171 ddrake@puyallupwa.gov
Engineering Commercial Standard Conditions Resolved Standard Conditions
* Prior to STARTING site work; request inspection for Erosion and Sediment. ** IF A DOUBLE DECTECTOR BACKFLOW ASSEMBLY IN NOT INSTALLED ON THE WATER SERVICE LINE FOR THE OFFICE (OR OVERALL SITE) THE INSTALLATION OF ONE IS REQUIRED. OCCUPANCY WILL NOT BE GRANTED UNTIL THIS IS TRUE ** ** IF A SAMPLING TEE IN NOT INSTALLED ON THE SEWER LATERAL FOR THE OFFICE (OR OVERALL SITE) THE INSTALLATION OF ONE IS REQUIRED. OCCUPANCY WILL NOT BE GRANTED UNTIL THIS IS TRUE ** * THE APPLICANT IS RESPONSIBLE TO SCHEDULE INSPECTIONS. UTILITY INSPECTIONS ARE REQUIRED PRIOR TO BACKFILLING. ** STORMWATER CONTROL OF ROOF DOWNSPOUTS MUST BE CONTROLLED. ALL WATERS COLLECTED MUST BE DIRECTED TO THE ONSITE STORMWATER POND ** ** SEDIMENT CONTROL AND EROSION PROCEDURES SHALL BE PRACTICE TO ELIMINATE AND PREVENT OFF SITE DAMAGE. STORMWATER RUNOFF ORIGINATING UPGRADE OF EXPOSED AREAS SHALL BE CONTROLLED TO REDUCE EROSION AND SEDIMENT LOSS DURING THE PERIOD OF EXPOSURE. * The builder/owner shall be responsible for keeping the existing right-of-way free of debris and dirt. Any violation of PMC Chapter 21.14 pertaining to clearing, filling and grading, erosion and sediment control, and storm water discharges shall be prosecuted to the fullest extent of the law. * Any addition/expansion to the foot print of the building including decks and porches not originally shown on the approved set of plans must obtain proper permits prior to construction. * The applicant is responsible to call the Utility Notification Center at 1-800-424-5555 before beginning any excavation. Call before you dig, it's the law. * No work shall be done in or on the public right of way without a licensed and bonded contractor first obtaining a right of way permit. * Any code requirement that may have been overlooked in this plan review does not imply that the requirements have been waived.
Miscellaneous Condition Resolved Prior to Issuance
Development & Permitting Services
Civil plan/SWPPP. LL 05/02/2022

Related Permit & Planning Applications

There are no related items for this permit application.

Documents & Images

Date Uploaded File Type Name
03/31/2022 Receipt Receipt for transaction:2022-000603
05/25/2022 Plans SEDIMENT AND EROSION CONTROL 02.03.3 (Flattened)
05/25/2022 Plans DDCVA 03.04.2 (Flattened)
05/25/2022 Report CCS-TF Civil-Doc_CSWPPP0 (Flattened)
08/03/2022 Receipt Receipt for transaction:2022-001499
11/02/2022 Plans Sampling Tee 04.03.04 (Stamped)
11/02/2022 Plans CCS-Office-Rev01-Drawing_Combined (Stamped)
11/02/2022 Form CCS Office-Rev01-Energy_Req'd List (Stamped)
11/02/2022 Form CCS Office-Rev01-Energy_Compliance (Stamped)
11/02/2022 Report CCS-Office-Doc_Structural Calc (Stamped)
11/02/2022 Plans CCS Office-Rev01-Truss_Layout (Stamped)
11/02/2022 Plans CCS Office-Rev01-TJI_Layout (Stamped)
11/02/2022 Plans CCS Office-Rev01-Truss_Calc (Stamped)
11/02/2022 Form CCS-Office-Doc_Fixture Worksheet (Stamped)
11/04/2022 Receipt Receipt for transaction:2022-002206
11/07/2022 Letter Permit Job Card
11/07/2022 Permit Permit - Detailed
11/07/2022 Permit Permit - Detailed
11/30/2022 PRCA20220580 Revised Site Plan 11292022 (STAMPED)
12/01/2022 Report Inspection Report (Footing/Setback Inspection)
12/01/2022 Report Inspection Report (Erosion And Sediment Inspection)
12/01/2022 Cascade Christian School Phasing plan 22-1129-CCS-Office-phase (STAMPED)
12/05/2022 Report Inspection Report (Footing/Setback Inspection)
12/09/2022 Report Inspection Report (Foundation/Rebar Inspection)
12/12/2022 Report Inspection Report (Foundation/Rebar Inspection)
12/16/2022 Report Inspection Report (Storm Inspection)
12/20/2022 Report Inspection Report (Underfloor Inspection)
02/23/2023 Form PRCA20220580-Permit Letter_Rev02
02/23/2023 Report Inspection Report (Mechanical Rough In Inspection)
02/23/2023 Report Inspection Report (Frame Inspection)
02/23/2023 Report Inspection Report (Plumbing Rough In Inspection)
02/27/2023 Receipt Receipt for transaction:2023-000305
03/06/2023 Form PRCA20220580_Rev02 Application0 (Flattened)
03/06/2023 Plans CCS Office-Rev02-Drawing_Mech (Stamped)
03/06/2023 Plans CCS Office-Rev02-Drawing_Arch_v2 (Stamped)
03/07/2023 Report Inspection Report (Mechanical Rough In Inspection)
03/07/2023 Report Inspection Report (Frame Inspection)
03/10/2023 Report Inspection Report (Energy (Insulation) Inspection)
03/16/2023 Report Inspection Report (Wallboard / Drywall Inspection)
05/01/2023 Report Inspection Report (Comment Building Div Inspection)
05/03/2023 Report Inspection Report (Engineering Final Inspection)
05/08/2023 Report Inspection Report (Building Final Inspection)
05/08/2023 Report Inspection Report (Building Final Inspection)
05/09/2023 Report Inspection Report (Building Final Inspection)
05/16/2023 Report Inspection Report (Storm Inspection)
05/17/2023 Report Inspection Report (Building Final Inspection)
07/12/2023 Report Inspection Report (Frame Inspection)
07/17/2023 Report Inspection Report (Firewall/Firestop Inspection)
07/18/2023 Report Inspection Report (Comment Building Div Inspection)
07/24/2023 Side sewer sample tee PIC
07/25/2023 Report Inspection Report (Water Service Inspection)
08/01/2023 Report Inspection Report (Water Service Inspection)
09/12/2023 Report 8-24-23 Backflow Test Report 815 21st St SE Puyallup CCS District Office
09/12/2023 Report Inspection Report (Engineering Final Inspection)
10/10/2023 Report Inspection Report (Building Final Inspection)
10/26/2023 Report Inspection Report (Building Final Inspection)


Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.