Review Type |
Outcome |
Est. Completion Date |
Completed |
Engineering Civil Review
|
Approved
|
01/10/2025
|
12/18/2024
|
|
|
|
1st Review
|
Engineering Traffic Review
|
Approved
|
01/10/2025
|
12/18/2024
|
|
|
|
|
Engineering Review
|
Approved
|
01/10/2025
|
12/18/2024
|
|
|
|
Add Submittal Item: Misc
Additional Submittal Item Required: Certificate of Water Availability. Per Puyallup Municipal Code 14.22.020, a certificate of water availability is required from Valley Water District, the site’s water purveyor. You can initiate the certificate request by completing the application found here: https://www.valleywaterdistrict.com/forms.php and submitting it to Valley Water District. [Yianni Charitou @ 08/29/2024 4:58 PM]
|
|
Other/Miscellaneous
The PRCNC20241019 building site plan must match the approved PRCCP20241109 civil plan. The superimposed civil design on the site plan shall be updated prior to Engineering approval of the PRCNC20241019 building permit application, even if it requires additional resubmissions. Please acknowledge that it is the applicant's responsibility to coordinate resubmissions of the building plan to avoid redundant reviews and fees prior to civil permit approval. [Yianni Charitou @ 10/02/2024 9:34 AM]
|
|
See Document Markup
Provide an exhibit depicting Northwest Pipeline Agreement #71165G104 for the specific encroachment of right of way per AFNs 201811070156 and 201803140436 regarding the 12" storm main, parking, landscaping, storm drain line, domestic well service line, water line, existing buildings, and other existing encroachments shown in the various exhibits of the recorded documents. Furthermore, provide a copy of the Northwest Pipeline Agreement authorizing the construction of the new facilities encroaching in the right of way including the play equipment, pond, path, fence, roof drain lines, clean outs, drive lanes, parking stalls, etc. The applicant shall contact Williams Gas' Matthew Kautzman at matt.kautzman@williams.com or (253) 377-6146 to schedule a survey of the gas pipeline easement adjacent to the property before construction is initiated. The applicant shall submit a copy of Matthew's survey approval to the City before proceeding with construction. [SITE PLAN, sheet A1.1]
|
|
See Document Markup
Depicted Valley Water Easement for Water Facilities does not match the recorded easement area in AFN 201908200089. There are small extruded areas missing (see lines labeled as L3, L4, L5, L21, L22, L23, L28, L29, and L30 in Exhibit "C"). Furthermore, please provide a signed letter from Valley Water District that the proposed improvements do not violate the encroachment/construction activity clause of the easement agreement which states that no structures shall be erected upon the easement, no obstructions (which may include parking vehicles) may encroach on the easement, or any trees, bushes, or shrubbery shall be planted or maintained within the easement. [SITE PLAN, sheet A1.1]
|
|
CityView system: 12/11/2024 2:28 PM - Activity assignment changed from 'Yianni Charitou' to 'Adam Hunt' due to employee availability configuration.
|
Fire Review
|
Approved
|
01/10/2025
|
12/16/2024
|
|
|
|
|
Planning Review
|
Approved
|
01/10/2025
|
12/11/2024
|
|
|
|
|
Plumbing Review
|
Approved
|
08/29/2024
|
10/23/2024
|
|
|
|
See Document Markup
Floor Drains; locations and trap seal details (typical) See A2.2 - Const. Plan Set PP101
|
|
See Document Markup
Floor Drain (typical) Please clarify how trap seal will be maintained. Details show trap primer, but trap primers are not scheduled or noted in supply plans. Const. Plan Set PP601
|
|
See Document Markup
|
|
|
Plumbing Review
|
Approved
|
10/29/2024
|
10/23/2024
|
|
|
|
See Document Markup
Floor Drains; locations and trap seal details (typical) See A2.2 - Const. Plan Set PP101
|
|
See Document Markup
Floor Drain (typical) Please clarify how trap seal will be maintained. Details show trap primer, but trap primers are not scheduled or noted in supply plans. Const. Plan Set PP601
|
|
See Document Markup
|
|
|
Building Review
|
Approved
|
10/29/2024
|
10/23/2024
|
|
|
|
See Document Markup
Please included fenced areas in exit route plans and/or verify compliance with the exceptions provided by 1028.5 Access to a public way. Please provide fence/gate details in door scheduled. Const. Plan Set G2.0.
|
|
See Document Markup
Please address pond details for building code compliance. Const. Plan Set L1.0
|
|
See Document Markup
Please add gates and gate hardware to the schedule; or other appropriate location. See note on G2.0 as applicable. Const. Set A7.1
|
|
See Document Markup
Review court yard exit path for exit signs and exit illumination IBC 1008.
Const. Plan E2.0
|
|
See Document Markup
Geo-technical Report please update for current project and applicable codes. Geotech Report -cover
|
|
See Document Markup
Divider Curtains;
1) Please verify flame/smoke rating per code; also address other wall coverings as applicable.
2) Please advise automatic fire sprinkler and smoke detection designers of potential impacts. Const. Plan Set A212
|
|
See Document Markup
Plans lack constructible details for accessibility. Please provide details for hardware, dimensional, slopes, elevations and clearance requirements. Include but not limited to fixtures, switches, counters, grades, clearances, etc. Const. Plan Set G1.0
|
|
See Document Markup
How is this glazing supported and secured (typical)? See IBC Chapt. 24 Const. Plan Set 2.24
|
|
See Document Markup
Please address compliance for IMC 304.11 Guards. Const Plan Set MH104
|
|
See Document Markup
Please review building code for exit discharge hardware, lighting, signage etc. Const. Plan Set L3.0
|
|
See Document Markup
Kitchen Equipment? Please provide equipment schedules to assess sanitation, ventilation, cross connection etc. Please address accessibly as applicable. Const. Plan Set A2.24
|
|
See Document Markup
After approval from the Owner and Architect, please provide contractors statement of responsibly for Building Official review. Const. Plan Set S1.0
|
|
See Document Markup
Please add typical ceiling details as applicable for ATC and clouds to address bracing, support and construction details. Const. Plan Set A2.12
|
|
See Document Markup
Plam studs. Please provide direction for cut/notch and boring limits. S2.1
|
|
See Document Markup
Please address compliance with IBC SECTION 429 ELECTRIC VEHICLE CHARGING INFRASTRUCTURE for new buildings. Const. Plan Set E1.0
|
|
See Document Markup
Occupant load capacity exceeds 100 on G0.2 - Please see 308.5 for I-4 classification. Please verify maximum number of children 2 1/2 years or under . Const. Plan set G0.1.
|
|
See Document Markup
Address numbers. Visible from the street with contrasting colors: 6 inches less than 50 feet - 12 inches 51-100.See PMC 16.04.25 for other sizes. Const. Plan Set A3.2
|
|
|
Engineering Review
|
Failed
|
10/29/2024
|
10/03/2024
|
|
|
|
Add Submittal Item: Misc
Additional Submittal Item Required: Certificate of Water Availability. Per Puyallup Municipal Code 14.22.020, a certificate of water availability is required from Valley Water District, the site’s water purveyor. You can initiate the certificate request by completing the application found here: https://www.valleywaterdistrict.com/forms.php and submitting it to Valley Water District. [Yianni Charitou @ 08/29/2024 4:58 PM]
|
|
Other/Miscellaneous
The PRCNC20241019 building site plan must match the approved PRCCP20241109 civil plan. The superimposed civil design on the site plan shall be updated prior to Engineering approval of the PRCNC20241019 building permit application, even if it requires additional resubmissions. Please acknowledge that it is the applicant's responsibility to coordinate resubmissions of the building plan to avoid redundant reviews and fees prior to civil permit approval. [Yianni Charitou @ 10/02/2024 9:34 AM]
|
|
See Document Markup
The PRCNC20241019 building site plan must match the approved PRCCP20241109 civil plan. Therefore, it is strongly recommended that the applicant submit a civil site plan drawing rather than the architectural drawings for the building permit site plan submittal item. The architectural site plan may be included in the construction plan set submittal item, but the civil drawings are better utilized in the standalone site plan submittal. The site plan must depict the new or existing public utility connections (i.e. water, sewer, stormwater) from the public right-of-way to the building(s) and other pertinent site information including easements and site constraints. [SITE PLAN, sheet A1.1]
|
|
See Document Markup
Include the tax parcel number (0420253071) on the site plan. [SITE PLAN, sheet A1.1]
|
|
See Document Markup
In accordance with pre-application meeting notes PLPRE20220076, the Uniform Plumbing Code, and City Design Standard 402.3, an external gravity grease interceptor is required to be designed by a professional engineer and installed on the side sewer per City Standard Details 04.06.01 and 04.06.02. Please revise the site plan to depict the location of the new or existing grease interceptor. A professional engineer shall provide gravity grease interceptor sizing calculations and a report stating that the new grease interceptor has adequate capacity to serve the site/project. You may submit a full menu for the City to consider an internal grease trap as an alternative to the external grease interceptor. The required pretreatment facilities are at the full discretion of the City. [SITE PLAN, sheet A1.1]
|
|
See Document Markup
Depict and label the Valley Water Easement for Water Facilities per AFN 201908200089. [SITE PLAN, sheet A1.1]
|
|
See Document Markup
Depict the easement area for the 10' power easement callout. [SITE PLAN, sheet A1.1]
|
|
See Document Markup
Label the 75' pipeline easement per AFN 1766023. [SITE PLAN, sheet A1.1]
|
|
See Document Markup
Provide an exhibit depicting Northwest Pipeline Agreement #71165G104 for the specific encroachment of right of way per AFNs 201811070156 and 201803140436 regarding the 12" storm main, parking, landscaping, storm drain line, domestic well service line, water line, existing buildings, and other existing encroachments shown in the various exhibits of the recorded documents. Furthermore, provide a copy of the Northwest Pipeline Agreement authorizing the construction of the new facilities encroaching in the right of way including the play equipment, pond, path, fence, roof drain lines, clean outs, drive lanes, parking stalls, etc. The applicant shall contact Williams Gas' Matthew Kautzman at matt.kautzman@williams.com or (253) 377-6146 to schedule a survey of the gas pipeline easement adjacent to the property before construction is initiated. The applicant shall submit a copy of Matthew's survey approval to the City before proceeding with construction. [SITE PLAN, sheet A1.1]
|
|
See Document Markup
No building permit or development permit shall be granted for the construction or substantial improvement of any industrial, commercial, or residential building, or plat unless the plans and specifications contain provisions for the dedication to the City of sufficient street right of way for the classification of the street abutting the property according to the street plans and street development needs of the city for that street. In accordance with Puyallup Municipal Code Chapter 11.08.120, the subject site property owner shall dedicate approximately 16.5 of right-of-way to match the 73 street classification of 33RD ST SE. Revise callout to indicate that 16.5' feet shall be dedicated to the City of Puyallup for both tax parcels. [SITE PLAN, sheet A1.1]
|
|
See Document Markup
The proposed building shall be served by Valley Water District, the site's water purveyor. The civil plans depict a fire and domestic water connection to the Puyallup water main in 33RD ST SE. Please remove the proposed Puyallup water connection and depict the Valley Water District connection on the site plan. [SITE PLAN, sheet A1.1]
|
|
See Document Markup
A separate and independent side sewer from the public main to all building sites shall be provided for each building per City Standards Section 401(7). The proposed learning center cannot share a side sewer with the existing force main connection from the other building(s). Depict and label the independent side sewer for the proposed learning center. [SITE PLAN, sheet A1.1]
|
|
See Document Markup
Identify and label the proposed under counter fixture. If it is a plumbing fixture, update the plumbing plans and plumbing fixture accordingly. [CONSTRUCTION PLAN SET, sheet A2.23]
|
|
See Document Markup
A separate and independent side sewer from the public main to all building sites shall be provided for each building per City Standards Section 401(7). The location of the independent side sewer for the learning center may change on the civil plans. Please compare to approved civil plans prior to final building permit submittal to avoid redundant reviews. [CONSTRUCTION PLAN SET, sheet PP101]
|
|
See Document Markup
The proposed building shall be served by Valley Water District, the site's water purveyor. The civil plans depict a fire and domestic water connection to the Puyallup water main in 33RD ST SE. The location of the Valley Water District water service for the learning center may change on the civil plans. Please compare to approved civil plans prior to final building permit submittal to avoid redundant reviews. [CONSTRUCTION PLAN SET, sheet PP101]
|
|
See Document Markup
Depict and label the six proposed floor drain waste line connections on the foundation plan. [CONSTRUCTION PLAN SET, sheet PP101]
|
|
See Document Markup
In accordance with pre-application meeting notes PLPRE20220076, the Uniform Plumbing Code, and City Design Standard 402.3, an external gravity grease interceptor is required to be designed by a professional engineer and installed on the side sewer per City Standard Details 04.06.01 and 04.06.02. A professional engineer shall provide gravity grease interceptor sizing calculations and a report stating that the new grease interceptor has adequate capacity to serve the site/project. You may submit a full menu for the City to consider an internal grease trap as an alternative to the external grease interceptor. The required pretreatment facilities are at the full discretion of the City. Furthermore, all fixtures, equipment, and drain lines located in a facility's food preparation and clean up area, which are sources of FOG, shall be connected to the grease trap. All pre-rinse and/or pre-wash sinks, sinks in dishwashing areas, two or three compartment sinks, wok stoves, self-cleaning stove ventilation/exhaust hood, kitchen floor drains, floor drains, floor sinks, mop sinks, food-prep sinks, hand sinks, and dishwashers must be connected to the grease trap or interceptor. No sanitary waste shall be conveyed to the grease trap or interceptor. Please revise the plumbing layout accordingly. [CONSTRUCTION PLAN SET, sheet PP101]
|
|
See Document Markup
Provide the quantity for each type of plumbing fixture to match the floor plans, plumbing plans, and plumbing fixture worksheet. According to the plans, there are 12 toilets, 12 lavatory sinks, 1 drinking fountain, 1 washing machine, 2 mop sinks, 6 floor drains, and 14 other sinks. [CONSTRUCTION PLAN SET, sheet PP601]
|
|
See Document Markup
Include proposed hub drain in the plumbing fixture schedule. [CONSTRUCTION PLAN SET, sheet PP601]
|
|
See Document Markup
Depicted Valley Water Easement for Water Facilities does not match the recorded easement area in AFN 201908200089. There are small extruded areas missing (see lines labeled as L3, L4, L5, L21, L22, L23, L28, L29, and L30 in Exhibit "C"). Furthermore, please provide a signed letter from Valley Water District that the proposed improvements do not violate the encroachment/construction activity clause of the easement agreement which states that no structures shall be erected upon the easement, no obstructions (which may include parking vehicles) may encroach on the easement, or any trees, bushes, or shrubbery shall be planted or maintained within the easement. [SITE PLAN, sheet A1.1]
|
|
|
Engineering Traffic Review
|
Approved
|
10/29/2024
|
10/03/2024
|
|
|
|
|
Fire Review
|
Approved
|
10/29/2024
|
10/02/2024
|
|
|
|
|
Planning Review
|
Approved
|
10/29/2024
|
10/02/2024
|
|
|
|
|
Engineering Review
|
Failed
|
08/29/2024
|
09/05/2024
|
|
|
|
Add Submittal Item: Misc
Additional Submittal Item Required: Certificate of Water Availability. Per Puyallup Municipal Code 14.22.020, a certificate of water availability is required from Valley Water District, the site’s water purveyor. You can initiate the certificate request by completing the application found here: https://www.valleywaterdistrict.com/forms.php and submitting it to Valley Water District. [Yianni Charitou @ 08/29/2024 4:58 PM]
|
|
Other/Miscellaneous
The PRCNC20241019 building site plan must match the approved PRCCP20241109 civil plan. Please acknowledge that it is the applicant's responsibility to coordinate resubmissions of the building plan to avoid redundant reviews and fees prior to civil permit approval. [Yianni Charitou @ 08/30/2024 10:03 AM]
|
|
See Document Markup
The PRCNC20241019 building site plan must match the approved PRCCP20241109 civil plan. Therefore, it is strongly recommended that the applicant submit a civil site plan drawing rather than the architectural drawings for the building permit site plan submittal item. The architectural site plan may be included in the construction plan set submittal item, but the civil drawings are better utilized in the standalone site plan submittal. The site plan must depict the new or existing public utility connections (i.e. water, sewer, stormwater) from the public right-of-way to the building(s) and other pertinent site information including easements and site constraints. [SITE PLAN, sheet A1.1]
|
|
See Document Markup
Include the tax parcel number (0420253071) on the site plan. [SITE PLAN, sheet A1.1]
|
|
See Document Markup
In accordance with pre-application meeting notes PLPRE20220076, the Uniform Plumbing Code, and City Design Standard 402.3, an external gravity grease interceptor is required to be designed by a professional engineer and installed on the side sewer per City Standard Details 04.06.01 and 04.06.02. Please revise the site plan to depict the location of the new or existing grease interceptor. A professional engineer shall provide gravity grease interceptor sizing calculations and a report stating that the new grease interceptor has adequate capacity to serve the site/project. You may submit a full menu for the City to consider an internal grease trap as an alternative to the external grease interceptor. The required pretreatment facilities are at the full discretion of the City. [SITE PLAN, sheet A1.1]
|
|
See Document Markup
Depict and label the Valley Water Easement for Water Facilities per AFN 201908200089. [SITE PLAN, sheet A1.1]
|
|
See Document Markup
Depict the easement area for the 10' power easement callout. [SITE PLAN, sheet A1.1]
|
|
See Document Markup
Label the 75' pipeline easement per AFN 1766023. [SITE PLAN, sheet A1.1]
|
|
See Document Markup
Provide an exhibit depicting Northwest Pipeline Agreement #71165G104 for the specific encroachment of right of way per AFNs 201811070156 and 201803140436 regarding the 12" storm main, parking, landscaping, storm drain line, domestic well service line, water line, existing buildings, and other existing encroachments shown in the various exhibits of the recorded documents. Furthermore, provide a copy of the Northwest Pipeline Agreement authorizing the construction of the new facilities encroaching in the right of way including the play equipment, pond, path, fence, roof drain lines, clean outs, etc. The applicant shall contact Williams Gas' Matthew Kautzman at matt.kautzman@williams.com or (253) 377-6146 to schedule a survey of the gas pipeline easement adjacent to the property before construction is initiated. The applicant shall submit a copy of Matthew's survey approval to the City before proceeding with construction. [SITE PLAN, sheet A1.1]
|
|
See Document Markup
No building permit or development permit shall be granted for the construction or substantial improvement of any industrial, commercial, or residential building, or plat unless the plans and specifications contain provisions for the dedication to the City of sufficient street right of way for the classification of the street abutting the property according to the street plans and street development needs of the city for that street. In accordance with Puyallup Municipal Code Chapter 11.08.120, the subject site property owner shall dedicate approximately 16.5 of right-of-way to match the 73 street classification of 33RD ST SE. Revise callout to indicate that 16.5' feet shall be dedicated to the City of Puyallup for both tax parcels. [SITE PLAN, sheet A1.1]
|
|
See Document Markup
The proposed building shall be served by Valley Water District, the site's water purveyor. The civil plans depict a fire and domestic water connection to the Puyallup water main in 33RD ST SE. Please remove the proposed Puyallup water connection and depict the Valley Water District connection on the site plan. [SITE PLAN, sheet A1.1]
|
|
See Document Markup
A separate and independent side sewer from the public main to all building sites shall be provided for each building per City Standards Section 401(7). The proposed learning center cannot share a side sewer with the existing force main connection from the other building(s). Depict and label the independent side sewer for the proposed learning center. [SITE PLAN, sheet A1.1]
|
|
See Document Markup
Identify and label the proposed under counter fixture. If it is a plumbing fixture, update the plumbing plans and plumbing fixture accordingly. [CONSTRUCTION PLAN SET, sheet A2.23]
|
|
See Document Markup
A separate and independent side sewer from the public main to all building sites shall be provided for each building per City Standards Section 401(7). The location of the independent side sewer for the learning center may change on the civil plans. Please compare to approved civil plans prior to final building permit submittal to avoid redundant reviews. [CONSTRUCTION PLAN SET, sheet PP101]
|
|
See Document Markup
The proposed building shall be served by Valley Water District, the site's water purveyor. The civil plans depict a fire and domestic water connection to the Puyallup water main in 33RD ST SE. The location of the Valley Water District water service for the learning center may change on the civil plans. Please compare to approved civil plans prior to final building permit submittal to avoid redundant reviews. [CONSTRUCTION PLAN SET, sheet PP101]
|
|
See Document Markup
Depict and label the six proposed floor drain waste line connections on the foundation plan. [CONSTRUCTION PLAN SET, sheet PP101]
|
|
See Document Markup
In accordance with pre-application meeting notes PLPRE20220076, the Uniform Plumbing Code, and City Design Standard 402.3, an external gravity grease interceptor is required to be designed by a professional engineer and installed on the side sewer per City Standard Details 04.06.01 and 04.06.02. A professional engineer shall provide gravity grease interceptor sizing calculations and a report stating that the new grease interceptor has adequate capacity to serve the site/project. You may submit a full menu for the City to consider an internal grease trap as an alternative to the external grease interceptor. The required pretreatment facilities are at the full discretion of the City. Furthermore, all fixtures, equipment, and drain lines located in a facility's food preparation and clean up area, which are sources of FOG, shall be connected to the grease trap. All pre-rinse and/or pre-wash sinks, sinks in dishwashing areas, two or three compartment sinks, wok stoves, self-cleaning stove ventilation/exhaust hood, kitchen floor drains, floor drains, floor sinks, mop sinks, food-prep sinks, hand sinks, and dishwashers must be connected to the grease trap or interceptor. No sanitary waste shall be conveyed to the grease trap or interceptor. Please revise the plumbing layout accordingly. [CONSTRUCTION PLAN SET, sheet PP101]
|
|
See Document Markup
Provide the quantity for each type of plumbing fixture to match the floor plans, plumbing plans, and plumbing fixture worksheet. According to the plans, there are 12 toilets, 12 lavatory sinks, 1 drinking fountain, 1 washing machine, 2 mop sinks, 6 floor drains, and 14 other sinks. [CONSTRUCTION PLAN SET, sheet PP601]
|
|
See Document Markup
Include proposed hub drain in the plumbing fixture schedule. [CONSTRUCTION PLAN SET, sheet PP601]
|
|
|
Building Review
|
Failed
|
08/29/2024
|
08/28/2024
|
|
|
|
See Document Markup
Please included fenced areas in exit route plans and/or verify compliance with the exceptions provided by 1028.5 Access to a public way. Please provide fence/gate details in door scheduled. Const. Plan Set G2.0.
|
|
See Document Markup
Please address pond details for building code compliance. Const. Plan Set L1.0
|
|
See Document Markup
Please add gates and gate hardware to the schedule; or other appropriate location. See note on G2.0 as applicable. Const. Set A7.1
|
|
See Document Markup
Review court yard exit path for exit signs and exit illumination IBC 1008.
Const. Plan E2.0
|
|
See Document Markup
Geo-technical Report please update for current project and applicable codes. Geotech Report -cover
|
|
See Document Markup
Divider Curtains;
1) Please verify flame/smoke rating per code; also address other wall coverings as applicable.
2) Please advise automatic fire sprinkler and smoke detection designers of potential impacts. Const. Plan Set A212
|
|
See Document Markup
Plans lack constructible details for accessibility. Please provide details for hardware, dimensional, slopes, elevations and clearance requirements. Include but not limited to fixtures, switches, counters, grades, clearances, etc. Const. Plan Set G1.0
|
|
See Document Markup
How is this glazing supported and secured (typical)? See IBC Chapt. 24 Const. Plan Set 2.24
|
|
See Document Markup
Please address compliance for IMC 304.11 Guards. Const Plan Set MH104
|
|
See Document Markup
Please review building code for exit discharge hardware, lighting, signage etc. Const. Plan Set L3.0
|
|
See Document Markup
Kitchen Equipment? Please provide equipment schedules to assess sanitation, ventilation, cross connection etc. Please address accessibly as applicable. Const. Plan Set A2.24
|
|
See Document Markup
After approval from the Owner and Architect, please provide contractors statement of responsibly for Building Official review. Const. Plan Set S1.0
|
|
See Document Markup
Please add typical ceiling details as applicable for ATC and clouds to address bracing, support and construction details. Const. Plan Set A2.12
|
|
See Document Markup
Plam studs. Please provide direction for cut/notch and boring limits. S2.1
|
|
See Document Markup
Please address compliance with IBC SECTION 429 ELECTRIC VEHICLE CHARGING INFRASTRUCTURE for new buildings. Const. Plan Set E1.0
|
|
See Document Markup
Occupant load capacity exceeds 100 on G0.2 - Please see 308.5 for I-4 classification. Please verify maximum number of children 2 1/2 years or under . Const. Plan set G0.1.
|
|
See Document Markup
Address numbers. Visible from the street with contrasting colors: 6 inches less than 50 feet - 12 inches 51-100.See PMC 16.04.25 for other sizes. Const. Plan Set A3.2
|
|
|
Fire Review
|
Approved
|
08/29/2024
|
08/21/2024
|
|
|
|
|
Engineering Traffic Review
|
Approved
|
08/29/2024
|
07/03/2024
|
|
|
|
See attached emails regarding traffic scoping, traffic impact fees and frontage requirements.
|
Planning Review
|
Approved
|
08/29/2024
|
07/03/2024
|
|
|
|
|
Building Review
|
Pending
|
01/10/2025
|
|
|
|
|
|
Plumbing Review
|
Pending
|
01/10/2025
|
|
|
|
|
|