CITY OF PUYALLUP PERMITTING PORTAL
Permit Application Status
PRPF20250508
| Paid Fees | Amount | Paid | Owing | Date Paid |
|---|---|---|---|---|
| Stormwater Inspection Fee | $360.00 | $360.00 | Paid | 06/05/2025 |
| Building Permit Fee | $1,161.75 | $1,161.75 | Paid | 06/05/2025 |
| Building Plan Review Fee | $755.14 | $755.14 | Paid | 04/22/2025 |
| Stormwater Report Review Fee | $360.00 | $360.00 | Paid | 04/22/2025 |
| WA State Building Code Council Fee (Commercial) | $25.00 | $25.00 | Paid | 06/05/2025 |
| Traffic Impact Fee (Commercial) | $119,250.00 | $119,250.00 | Paid | 06/05/2025 |
| Water System Development Charge | $22,188.79 | $22,188.79 | Paid | 06/05/2025 |
| Sewer System Development Charge | $22,585.13 | $22,585.13 | Paid | 06/05/2025 |
| Resubmittal/Revision Fee | $180.00 | $180.00 | Paid | 05/12/2025 |
| Resubmittal/Revision Fee | $180.00 | $180.00 | Paid | 07/22/2025 |
| Resubmittal/Revision Fee | $180.00 | $180.00 | Paid | 08/19/2025 |
| Outstanding Fees | Amount | Paid | Owing | Date Paid |
| No outstanding fees. | ||||
| Totals: | $167,225.81 | $167,225.81 | $0.00 |
Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.
$0.00
| Inspection | Outcome | Requested | Scheduled | Date Inspected |
|---|---|---|---|---|
| Plumbing Rough In Inspection | Not Ready | 6/25/2025 | 6/25/2025 | 06/25/2025 |
| Shannon King ((253) 840-6684) | ||||
| Manufactured Or Modular Structure Setup | Not Ready | 7/29/2025 | 7/29/2025 | 07/29/2025 |
| Shannon King ((253) 840-6684) | ||||
| Manufactured Or Modular Structure Setup | Not Ready | 8/4/2025 | 8/4/2025 | 08/04/2025 |
| James LaVergne ((253) 841-5590) | ||||
|
Corrections:
Other/Miscellaneous
Carried Forward
08/04/2025
1. Inspection for buildings 3&4, only.
2. provide Geotech report required for soil anchors
3. complete per pads per city's plans.
4. not ready
|
||||
| Manufactured Or Modular Structure Setup | Failed | 8/8/2025 | 8/8/2025 | 08/08/2025 |
| James LaVergne ((253) 841-5590) | ||||
|
Corrections:
Other/Miscellaneous
Carried Forward
08/08/2025
1. Inspection for buildings 3&4, only.
2. provide Geotech report required for soil anchors
3. complete per pads per city's plans.
4. not ready
|
||||
|
Other/Miscellaneous
Carried Forward
08/08/2025
1. need engineering approval for barring on curb
2. provide engineering approval on leaning cmu supports.
3. Inspection on unit 9 and 10.
|
||||
| Manufactured Or Modular Structure Setup | Not Ready | 8/12/2025 | 8/12/2025 | 08/12/2025 |
| Shannon King ((253) 840-6684) | ||||
|
Corrections:
Other/Miscellaneous
Carried Forward
08/12/2025
cancel per contractor.
|
||||
| Manufactured Or Modular Structure Setup | Partial Pass | 8/21/2025 | 8/21/2025 | 08/21/2025 |
| Shannon King ((253) 840-6684) | ||||
|
Corrections:
Other/Miscellaneous
Carried Forward
08/21/2025
cancel per contractor.
|
||||
| Manufactured Or Modular Structure Setup | Partial Pass | 8/22/2025 | 8/22/2025 | 08/22/2025 |
| Monty Johnson ((253) 770-3326) | ||||
|
Corrections:
Other/Miscellaneous
Carried Forward
08/22/2025
cancel per contractor.
|
||||
|
Other/Miscellaneous
Carried Forward
08/22/2025
7 thru 10 ok minus plumbing test as discussed
|
||||
| Plumbing Rough In Inspection | Passed | 8/25/2025 | 8/25/2025 | 08/25/2025 |
| James LaVergne ((253) 841-5590) | ||||
| Fire Final Inspection | Failed | 8/27/2025 | 08/27/2025 | |
| Ray Cockerham ((253) 841-5585) | ||||
|
Corrections:
Other/Miscellaneous
Carried Forward
08/27/2025
1) Exit light test required. Reviewed several lights; need to be serviced for testing.
2) Portable Identification; post portable numbers visible from fire access. 4-inch characters minimum.
3) Fire Extinguishers - Tag as NEW with date or use an indelible marker on the tank NEW with Date.
|
||||
| Manufactured Or Modular Structure Setup | Failed | 8/28/2025 | 8/28/2025 | 08/28/2025 |
| Ray Cockerham ((253) 841-5585) | ||||
|
Corrections:
Other/Miscellaneous
Carried Forward
08/28/2025
cancel per contractor.
|
||||
|
Other/Miscellaneous
Carried Forward
08/28/2025
1) Some exit lighting and exit signs are not working in PE 17; PE 14 and PE 22 and Men’s room at PE26? (One of the men’s restrooms had the device removed from the wall).
2) On accessible routes: openings at thresholds and others as applicable are limited to ½ inch maximum. This an excerpt of code from the 2021 IBC. https://codes.iccsafe.org/content/IBCACCPB2024P1/chapter-3-building-blocks#IBCACCPB2024P1_Pt03_Ch03_Sec302.3
3) Hazardous Locations: Glazing that is within 60 inches of the walking surface and does not meet the exception of 18 inches clear between the guard and the glazing is considered hazardous. Hazard glazing https://codes.iccsafe.org/content/IBC2021P2/chapter-24-glass-and-glazing#IBC2021P2_Ch24_Sec2406.4 and https://codes.iccsafe.org/content/IBC2021P2/chapter-24-glass-and-glazing#IBC2021P2_Ch24_Sec2406.4.6
For temporary solutions, please provide a concept that protects the exterior on the ramp/stair side.
4) Gaps and openings into the crawlspace and structure; please continue to seal. Review in accordance with manufacture and applicable standards to seal openings into the structure (noted at hollow framed doors) and the crawlspace.
5) Fire Final is complete less verification of the device map at the main fire alarm panel, this item will not delay occupancy.
6) Playground – need a review of the playground code requires an accessible access to the play area. I will take a look tomorrow. https://codes.iccsafe.org/lookup/content-id/35128943 & https://codes.iccsafe.org/content/IBC2021P2/chapter-11-accessibility#IBC2021P2_Ch11_Sec1111.4.13
7) Engineering, Planning and TPCHD approvals are required.
8) Work was continuing competing the ventilation at the skirting. Continued progress is expected.
|
||||
| Fire Final Inspection | Passed | 8/28/2025 | 8/28/2025 | 08/28/2025 |
| Ray Cockerham ((253) 841-5585) | ||||
|
Corrections:
Other/Miscellaneous
Resolved
08/28/2025
1) Exit light test required. Reviewed several lights; need to be serviced for testing.
2) Portable Identification; post portable numbers visible from fire access. 4-inch characters minimum.
3) Fire Extinguishers - Tag as NEW with date or use an indelible marker on the tank NEW with Date.
|
||||
| Manufactured Or Modular Structure Setup | Failed | 8/29/2025 | 8/29/2025 | 08/31/2025 |
| Ray Cockerham ((253) 841-5585) | ||||
|
Corrections:
Other/Miscellaneous
Carried Forward
08/31/2025
cancel per contractor.
|
||||
|
Other/Miscellaneous
Resolved
08/31/2025
1) Some exit lighting and exit signs are not working in PE 17; PE 14 and PE 22 and Men’s room at PE26? (One of the men’s restrooms had the device removed from the wall).
2) On accessible routes: openings at thresholds and others as applicable are limited to ½ inch maximum. This an excerpt of code from the 2021 IBC. https://codes.iccsafe.org/content/IBCACCPB2024P1/chapter-3-building-blocks#IBCACCPB2024P1_Pt03_Ch03_Sec302.3
3) Hazardous Locations: Glazing that is within 60 inches of the walking surface and does not meet the exception of 18 inches clear between the guard and the glazing is considered hazardous. Hazard glazing https://codes.iccsafe.org/content/IBC2021P2/chapter-24-glass-and-glazing#IBC2021P2_Ch24_Sec2406.4 and https://codes.iccsafe.org/content/IBC2021P2/chapter-24-glass-and-glazing#IBC2021P2_Ch24_Sec2406.4.6
For temporary solutions, please provide a concept that protects the exterior on the ramp/stair side.
4) Gaps and openings into the crawlspace and structure; please continue to seal. Review in accordance with manufacture and applicable standards to seal openings into the structure (noted at hollow framed doors) and the crawlspace.
5) Fire Final is complete less verification of the device map at the main fire alarm panel, this item will not delay occupancy.
6) Playground – need a review of the playground code requires an accessible access to the play area. I will take a look tomorrow. https://codes.iccsafe.org/lookup/content-id/35128943 & https://codes.iccsafe.org/content/IBC2021P2/chapter-11-accessibility#IBC2021P2_Ch11_Sec1111.4.13
7) Engineering, Planning and TPCHD approvals are required.
8) Work was continuing competing the ventilation at the skirting. Continued progress is expected.
|
||||
|
Other/Miscellaneous
Outstanding
08/31/2025
From previous correction:
Items 1, 2, 4, 5, 8 are completed for TCO.
3)Hazardous Locations: Glazing that is within 60 inches of the walking surface and does not meet the exception of 18 inches clear between the guard and the glazing is considered hazardous. Hazard glazing https://codes.iccsafe.org/content/IBC2021P2/chapter-24-glass-and-glazing#IBC2021P2_Ch24_Sec2406.4 and https://codes.iccsafe.org/content/IBC2021P2/chapter-24-glass-and-glazing#IBC2021P2_Ch24_Sec2406.4.6
For temporary solutions, please provide a concept that protects the exterior on the ramp/stair side.
***Temporary solution, see email dated 8/29/2025. Okay for TCO subject to reinspection when requested.
6) Playground – need a review of the playground code requires an accessible access to the play area. I will take a look tomorrow. https://codes.iccsafe.org/lookup/content-id/35128943 & https://codes.iccsafe.org/content/IBC2021P2/chapter-11-accessibility#IBC2021P2_Ch11_Sec1111.4.13
***Applicant has vergbally proposed an accessible route. Follow up will verify route.
7) Engineering, Planning and TPCHD approvals are required.
***Unresolved
|
||||
| Storm Inspection | Passed | 09/02/2025 | ||
| Jeff Hill ((253) 204-5633) | ||||
| Engineering Final Inspection | Passed | 09/02/2025 | ||
| Jeff Hill ((253) 204-5633) | ||||
| Planning Final Inspection | VOID | 09/02/2025 | ||
| Nabila Comstock ((253) 770-3361) | ||||
| Building Final Inspection | Partial Pass | 9/3/2025 | 9/3/2025 | 09/03/2025 |
| Ray Cockerham ((253) 841-5585) | ||||
|
Corrections:
Other/Miscellaneous
Carried Forward
09/03/2025
TCO approved for 30 calendar days.
From previous correction:
Items 1, 2, 4, 5, 7, 8 are completed for CO.
TCO approved for 30 calendar days. Expires Friday October 3rd.
3)Hazardous Locations:
***Temporary solution, see email dated 8/29/2025. Okay for TCO subject to reinspection when requested.
6) Playground – Accommodation is need per State code for new equipment. https://codes.iccsafe.org/lookup/content-id/35128943 & https://codes.iccsafe.org/content/IBC2021P2/chapter-11-accessibility#IBC2021P2_Ch11_Sec1111.4.13
***Applicant has verbally proposed an accessible route. Follow up with architect and construct route, design, slopes, grade and surface to code standards.
|
||||
| Building Final Inspection | Partial Pass | 9/30/2025 | 9/30/2025 | 09/30/2025 |
| Ray Cockerham ((253) 841-5585) | ||||
|
Corrections:
Other/Miscellaneous
Carried Forward
09/30/2025
TCO approved for 30 calendar days.
From previous correction:
Items 1, 2, 4, 5, 7, 8 are completed for CO.
TCO approved for 30 calendar days. Expires Friday October 3rd.
3)Hazardous Locations:
***Temporary solution, see email dated 8/29/2025. Okay for TCO subject to reinspection when requested.
6) Playground – Accommodation is need per State code for new equipment. https://codes.iccsafe.org/lookup/content-id/35128943 & https://codes.iccsafe.org/content/IBC2021P2/chapter-11-accessibility#IBC2021P2_Ch11_Sec1111.4.13
***Applicant has verbally proposed an accessible route. Follow up with architect and construct route, design, slopes, grade and surface to code standards.
|
||||
| Building Final Inspection | Passed | 10/1/2025 | 10/1/2025 | 10/01/2025 |
| James LaVergne ((253) 841-5590) | ||||
|
Corrections:
Other/Miscellaneous
Resolved
10/01/2025
TCO approved for 30 calendar days.
From previous correction:
Items 1, 2, 4, 5, 7, 8 are completed for CO.
TCO approved for 30 calendar days. Expires Friday October 3rd.
3)Hazardous Locations:
***Temporary solution, see email dated 8/29/2025. Okay for TCO subject to reinspection when requested.
6) Playground – Accommodation is need per State code for new equipment. https://codes.iccsafe.org/lookup/content-id/35128943 & https://codes.iccsafe.org/content/IBC2021P2/chapter-11-accessibility#IBC2021P2_Ch11_Sec1111.4.13
***Applicant has verbally proposed an accessible route. Follow up with architect and construct route, design, slopes, grade and surface to code standards.
|
||||
| Manufactured Or Modular Structure Setup | VOID | 10/02/2025 | ||
| James LaVergne ((253) 841-5590) | ||||
|
Corrections:
Other/Miscellaneous
Resolved
09/03/2025
cancel per contractor.
|
||||
|
Other/Miscellaneous
Resolved
09/03/2025
1) Some exit lighting and exit signs are not working in PE 17; PE 14 and PE 22 and Men’s room at PE26? (One of the men’s restrooms had the device removed from the wall).
2) On accessible routes: openings at thresholds and others as applicable are limited to ½ inch maximum. This an excerpt of code from the 2021 IBC. https://codes.iccsafe.org/content/IBCACCPB2024P1/chapter-3-building-blocks#IBCACCPB2024P1_Pt03_Ch03_Sec302.3
3) Hazardous Locations: Glazing that is within 60 inches of the walking surface and does not meet the exception of 18 inches clear between the guard and the glazing is considered hazardous. Hazard glazing https://codes.iccsafe.org/content/IBC2021P2/chapter-24-glass-and-glazing#IBC2021P2_Ch24_Sec2406.4 and https://codes.iccsafe.org/content/IBC2021P2/chapter-24-glass-and-glazing#IBC2021P2_Ch24_Sec2406.4.6
For temporary solutions, please provide a concept that protects the exterior on the ramp/stair side.
4) Gaps and openings into the crawlspace and structure; please continue to seal. Review in accordance with manufacture and applicable standards to seal openings into the structure (noted at hollow framed doors) and the crawlspace.
5) Fire Final is complete less verification of the device map at the main fire alarm panel, this item will not delay occupancy.
6) Playground – need a review of the playground code requires an accessible access to the play area. I will take a look tomorrow. https://codes.iccsafe.org/lookup/content-id/35128943 & https://codes.iccsafe.org/content/IBC2021P2/chapter-11-accessibility#IBC2021P2_Ch11_Sec1111.4.13
7) Engineering, Planning and TPCHD approvals are required.
8) Work was continuing competing the ventilation at the skirting. Continued progress is expected.
|
||||
| Building Final Inspection | VOID | 10/02/2025 | ||
| James LaVergne ((253) 841-5590) | ||||
| Condition | Status | Category |
|---|---|---|
| Building Permit Standard Conditions | Open | Standard Conditions |
|
Building Division
* Final approval by the Building Official is required prior to use or occupancy.* Work shall not proceed until the inspector has approved the stages of construction.* Surface storm water shall be diverted from the building site and shall not drain onto adjacent properties.* I hereby acknowledge that I have read this Permit/Application, that the information given is correct; that I am the owner or the duly authorized agent of the owner; that plans submitted herewith are in compliance with all applicable city, county and state laws and that all construction will proceed in accordance with said laws. This permit shall expire if work is not commenced with 180 days or if the work is suspended for a period of 180 days. Permits expire two years from issuance. * By leaving the contractor information section blank, I hereby certify further that contractors (general or subcontractors) will not be hired to perform any work in association with this permit. I also certify that if I do choose to hire a contractor (general or subcontractor) I will only hire those contractors that are licensed by the State of Washington. If you are a property owner, contractor or permittee and you are paying for someone to perform the work, they must have a valid contractor registration and the person(s) installing plumbing inside a structure must meet the plumbing certification requirements. If you have any questions regarding these regulations, you may contact the Washington State Department of Labor and Industries or you can find more information on-line at: http://www.lni.wa.gov/TradesLicensing/Contractors/HireCon/default.asp
|
||
| Miscellaneous Condition | Resolved | Submit With Civil Permit Application |
|
Development & Permitting Services
The addition of 4 more portables will again require updating of the civil plans. All new construction must be shown as one cohesive project on the civil plans and represented consistently throughout all of the submitted civil documents. All details including - but not limited to - downspout routing for roof runoff, stabilization of the existing ground, ADA accessibility to the ramps of the newest portables (walkways?) and utility routing for the bathroom facilities shall be shown on civil plans.
|
||
| Miscellaneous Condition | Resolved | Prior to Issuance |
|
Traffic Division
Issuance of this building permit is dependent upon Conditional Use Permit approval (PLCUP20240037). With the approval of the current CUP proposal (PLCUP20240037), the vested capacity would increase to 1341 students.
|
||
| Fire Review Conditions | Open | Standard Conditions |
|
Development & Permitting Services
• A minimum of one 2a-10bc fire extinguisher is required in each room
• A fire alarm system is required
• A separate permit is required for fire alarm
Schedule your inspection online through the city of puyallup online permit system. This is a request for inspection only. A date and time will be selected by Inspector depending on availability. Email morning of inspection between 7am – 8am for scheduled date and time. Fire Inspections are Monday – Thursday there will be no inspections on Fridays.
David Drake ddrake@puyallupwa.gov
|
||
| Miscellaneous Condition | Resolved | Prior to Issuance |
|
Engineering Division
Building permit PRPF20241230 cannot be issued until civil construction permit PRCCP20241229 is issued first.
|
||
| Miscellaneous Condition | Resolved | Prior to Completion |
|
Engineering Division
Occupancy shall not be granted until all civil work associated with PRCCP20241229 has been completed and approval has been provided.
|
||
| Miscellaneous Condition | Resolved | Prior to Issuance |
|
Planning Division
Permit may not be issued until hearing examiner issued an approval or approval with conditions of associated conditional use permit: PLCUP20240037
|
||
Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.