Summary

PRFA20251711
Fire Alarms
In Plan Check
CRP/TP BRADLEY HEIGHTS OWNER LLC
New
1. PROVIDE AND INSTALL NEW SILENT KNIGHT 6808 FIRE ALARM CONTROL PANEL AND HONEYWELL HPF-PS10 REMOTE POWER SUPPLY FOR OCCUPANT NOTIFICATION.2. PROVIDE AND INSTALL 6 STROBE ONLY NOTIFICATION APPLIANCES.3. PROVIDE AND INSTALL 44 LOW FREQUENCY SOUNDER NOTIFICATION APPLIANCES.4. PROVIDE AND INSTALL 30 HORN/STROBE NOTIFICATION APPLIANCES & 1 WATERFLOW BELL.5. PROVIDE AND INSTALL 19 MANUAL PULL STATIONS6. PROVIDE AND INSTALL 1 SMOKE DETECTOR FOR FACP AND PS107. PROVIDE AND INSTALL 2 DUAL-INPUT MODULES.8. PROVIDE AND INSTALL A HONEYWELL HW-AV-LTE-M CELLULAR COMMUNICATOR.9. INSPECT AND CERTIFY SYSTEM.BRADLEY HEIGHTS APARTMENTS - BLDG G
12/24/2025

Locations

Address
206 27TH AVE SE, Unit: G102, PUYALLUP, WA 98374

Address
206 27TH AVE SE, Unit: G103, PUYALLUP, WA 98374

Address
206 27TH AVE SE, Unit: G104, PUYALLUP, WA 98374

Address
206 27TH AVE SE, Unit: G105, PUYALLUP, WA 98374

Address
206 27TH AVE SE, Unit: G106, PUYALLUP, WA 98374

Address
206 27TH AVE SE, Unit: G107, PUYALLUP, WA 98374

Address
206 27TH AVE SE, Unit: G108, PUYALLUP, WA 98374

Address
206 27TH AVE SE, Unit: G109, PUYALLUP, WA 98374

Address
206 27TH AVE SE, Unit: G110, PUYALLUP, WA 98374

Address
206 27TH AVE SE, Unit: G111, PUYALLUP, WA 98374

Address
206 27TH AVE SE, Unit: G112, PUYALLUP, WA 98374

Address
206 27TH AVE SE, Unit: G201, PUYALLUP, WA 98374

Address
206 27TH AVE SE, Unit: G202, PUYALLUP, WA 98374

Address
206 27TH AVE SE, Unit: G203, PUYALLUP, WA 98374

Address
206 27TH AVE SE, Unit: G204, PUYALLUP, WA 98374

Address
206 27TH AVE SE, Unit: G205, PUYALLUP, WA 98374

Address
206 27TH AVE SE, Unit: G206, PUYALLUP, WA 98374

Address
206 27TH AVE SE, Unit: G207, PUYALLUP, WA 98374

Address
206 27TH AVE SE, Unit: G208, PUYALLUP, WA 98374

Address
206 27TH AVE SE, Unit: G209, PUYALLUP, WA 98374

Address
206 27TH AVE SE, Unit: G210, PUYALLUP, WA 98374

Address
206 27TH AVE SE, Unit: G211, PUYALLUP, WA 98374

Address
206 27TH AVE SE, Unit: G212, PUYALLUP, WA 98374

Address
206 27TH AVE SE, Unit: G301, PUYALLUP, WA 98374

Address
206 27TH AVE SE, Unit: G302, PUYALLUP, WA 98374

Address
206 27TH AVE SE, Unit: G303, PUYALLUP, WA 98374

Address
206 27TH AVE SE, Unit: G304, PUYALLUP, WA 98374

Address
206 27TH AVE SE, Unit: G305, PUYALLUP, WA 98374

Address
206 27TH AVE SE, Unit: G306, PUYALLUP, WA 98374

Address
206 27TH AVE SE, Unit: G307, PUYALLUP, WA 98374

Address
206 27TH AVE SE, Unit: G308, PUYALLUP, WA 98374

Address
206 27TH AVE SE, Unit: G309, PUYALLUP, WA 98374

Address
206 27TH AVE SE, Unit: G310, PUYALLUP, WA 98374

Address
206 27TH AVE SE, Unit: G311, PUYALLUP, WA 98374

Address
206 27TH AVE SE, Unit: G312, PUYALLUP, WA 98374

Property
0419036006

Address
206 27TH AVE SE, Unit: G101, PUYALLUP, WA 98374

Reviews

Review Type Outcome Est. Completion Date Completed
Fire Review Failed 03/09/2026 03/02/2026
Fire Review Pending 04/09/2026

Fees

Paid Fees Amount Paid Owing Date Paid
Fire Alarm Systems (New) Fee $517.50 $517.50 Paid 12/24/2025
Resubmittal/Revision Fee $180.00 $180.00 Paid 03/27/2026
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

There are no inspections for this development permit application, or you are not authorized to view them.

Conditions

Condition Status Category
New Fire Alarm System Conditions Open Standard Conditions
Fire Prevention
1- APPOINTMENT REQUIRED FOR ALL INSPECTIONS 2- PROVIDE PLANS AND PERMIT ON SITE FOR INSPECTION. 3- COMPLETE LABOR AND INDUSTRIES INSPECTIONS PRIOR TO REQUESTING CITY INSPECTION. 4- A REMOTE ANNUCIATOR LOCATED ON THE EXTERIOR OF THE MAIN ENTRANCE IN A WEATHER PROOF HOUSING REQUIRED. 5- EXTERIOR FIRE BELL REQUIRED OUTSIDE FIRE SPRINKLER ROOM. 6- DEVICE MAPS REQUIRED AT THE ANNUNCIATOR AND FIRE ALARM PANEL PRIOR TO CALLING IN FINAL. THE ANNUNCIATOR MAP WILL NEED TO BE WEATHER PROOF. 7- TOTAL COVERAGE IS REQURED; SUBJECT TO FIELD INSPECTION. COMPLY WITH NFPA 72, 2013 8- FIRE ALARM SYSTEM SHALL BE PLACARDED PER NFPA 72. THE UL CERTIFICATE SHALL BE POSTED AT TIME OF FINAL INSPECTION. THE SYSTEM WILL NEED TO BE UL CERTIFIED. 9- A PRE-TEST SHALL BE CONDUCTED AND A PRINT OUT OF THE LOCATION OF THE DEVICE, POINT NUMBER AND DESCRIPTOR SHALL BE FURNISHED TO THE INSPECTOR AT FINAL. 10- FIRE SPRINKLER TAMPER VALVES AND PIV WILL BE REQUIRED TO BE TESTED AT INSPECTION. FIRE SPRINKLER CONTRACTOR TO BE ONSITE. 11- THE CITY OF PUYALLUP ALLOWS ONE FACP PER BUILDING. THE PANEL WILL NEED TO BE LARGE ENOUGH TO HANDLE MULTIPLE TENTANTS IF APPLICABLE.

Related Permit & Planning Applications

Reference Number Status Type
PRDE20230753 Closed Demolition
PRFUP20230968 Permit(s) Issued Franchise Utility Permit
PROLP20231232 Closed Oversized Load/House Move Permit
PRDE20231242 Closed Demolition
PRUSR20231244 Canceled Utility Service Repair/PRIVATE PROPERTY ONLY
PRUSR20231267 Closed Utility Service Repair/PRIVATE PROPERTY ONLY
PRCNC20240278 Permit(s) Issued Commercial - New Construction
PRMU20240279 Permit(s) Issued Residential - New Multi-Unit
PRMU20240280 Permit(s) Issued Residential - New Multi-Unit
PRMU20240281 Permit(s) Issued Residential - New Multi-Unit
PRMU20240282 Permit(s) Issued Residential - New Multi-Unit
PRMU20240283 Permit(s) Issued Residential - New Multi-Unit
PRMU20240284 Permit(s) Issued Residential - New Multi-Unit
PRMU20240285 Permit(s) Issued Residential - New Multi-Unit
PRMU20240286 Permit(s) Issued Residential - New Multi-Unit
PRCCP20240845 Permit(s) Issued Civil Construction Permit
PRAMR20241578 Canceled Alternative Methods / Materials Request
PRAMR20250141 Closed Alternative Methods / Materials Request
PRRWF20250214 Permit(s) Issued Retaining Wall
PRRWF20250216 Permit(s) Issued Retaining Wall
PRRWF20250217 Permit(s) Issued Retaining Wall
PRRWF20250233 Permit(s) Issued Retaining Wall
PRRWF20250235 Permit(s) Issued Retaining Wall
PRRWF20250237 Permit(s) Issued Retaining Wall
PRFS20251283 Permit(s) Issued Fire Sprinklers
PRFS20251315 Permit(s) Issued Fire Sprinklers
PRFS20251469 Permit(s) Issued Fire Sprinklers
PRFS20251470 Permit(s) Issued Fire Sprinklers
PRFS20251577 Permit(s) Issued Fire Sprinklers
PRFA20251591 Permit(s) Issued Fire Alarms
PRFS20251594 Permit(s) Issued Fire Sprinklers
PRFS20251597 Permit(s) Issued Fire Sprinklers
PRPO20260015 Permit(s) Issued Pool/Hot Tub
PRCNC20260042 Returned for Correction Commercial - New Construction
PRCNC20260043 Returned for Correction Commercial - New Construction
PRCNC20260044 Returned for Correction Commercial - New Construction
PRCNC20260045 Ready for Issuance Commercial - New Construction
PRCNC20260047 Ready for Issuance Commercial - New Construction
PRCNC20260048 Ready for Issuance Commercial - New Construction
PRCP20260223 Ready for Issuance Carport
PRFA20260236 In Plan Check Fire Alarms
PRCP20260239 In Plan Check Carport
PRCP20260242 In Plan Check Carport
PRCP20260244 In Plan Check Carport
PRCP20260245 In Plan Check Carport
PRCP20260246 In Plan Check Carport
PRCP20260247 In Plan Check Carport
PRCP20260250 In Plan Check Carport
PRCP20260251 In Plan Check Carport
PRCP20260252 In Plan Check Carport
PRCP20260253 In Plan Check Carport
PRCP20260254 In Plan Check Carport
PRCP20260257 In Plan Check Carport
PRCP20260264 In Plan Check Carport
PRCP20260265 In Plan Check Carport
PRCP20260266 In Plan Check Carport
PRCP20260267 In Plan Check Carport
PRCP20260269 In Plan Check Carport
PRCP20260270 In Plan Check Carport
PRCP20260271 In Plan Check Carport
PRFA20260294 In Plan Check Fire Alarms
P-19-0105 Expired Pre-Application
P-21-0098 File Closed Pre-Application
PLDDG20220021 File Closed Downtown Design Review
PLPSP20220049 File Closed Preliminary Site Plan

Documents & Images

Date Uploaded File Type Name
12/24/2025 Form APPLICATION FORM
12/24/2025 Receipt Receipt for transaction:2025-002431
12/24/2025 Letter Incomplete Submittal Notice
02/04/2026 Letter Incomplete Submittal Notice
03/03/2026 Letter Permit Review Correction Letter
03/27/2026 Receipt Receipt for transaction:2026-000531


Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.