CITY OF PUYALLUP PERMITTING PORTAL

Development Permit Application Status

PRFS20240598


In order to request inspections, you need to be signed in.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRFS20240598
Fire Sprinklers
Permit(s) Issued
BCC PUYALLUP LLC
Addition
Adding a double interlock pre-action system to the building to protect the new UPS & Battery rooms per NFPA#13-2019 and City of Puyallup standards. - CENTERIS VOLTAGE PARK
04/09/2024
05/01/2024
11/05/2024

Locations

Reviews

Documents Returned For Corrections

Date Returned Name
04/30/2024 SPRINKLER PLANS (Stamped)
04/30/2024 CUT SHEETS (Stamped)
Review Type Outcome Est. Completion Date Completed
Fire Review Approved 05/07/2024 04/30/2024

Fees

Paid Fees Amount Paid Owing Date Paid
Automatic Fire-Extinguishing System (New) Permit Fee $265.25 $265.25 Paid 05/01/2024
Automatic Fire-Extinguishing System (New) Plan Review Fee $172.41 $172.41 Paid 04/09/2024
Building Division Fee (Hourly) $540.00 $540.00 Paid 04/16/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Fire Sprinkler Dry System Trip Test Pending
David Drake ((253) 864-4171)
Fire Sprinkler Final Inspection Pending
David Drake ((253) 864-4171)
Fire Sprinkler Cover Inspection Pending 5/10/2024 5/13/2024
David Drake ((253) 864-4171)
Hydrostatic Test 200Lbs 2Hrs Pending 5/10/2024 5/13/2024
David Drake ((253) 864-4171)
Fire Sprinkler
Outstanding
05/08/2024
Good morning, There are multiple fire sprinkler heads that have obstructions in these rooms. In order not to derail this project I need the fire sprinkler designer to come out onsite and determine how to make this system code compliant with the amount of obstructions created. The wire trays along with wiring are not yet complete and will add another layer of obstructions to this issue once installed. If there is a code compliant path that all these obstructions are allowed, please provide a fully detailed report from your company stating code sections, exemptions, alternative methods, dimensions, or whatever you feel makes this code compliant to me. Please make it PDF attached in an email. At the end of this project we are requiring the FPE (Fire Protection Engineer of record) to complete a close out report stating everything that was addressed is code compliant. This possibly could be a huge derailment at the end. Leonard, I've attached you to this email in hopes you can help with a code path, or fixes to move forward.

Hydrostatic Test 200Lbs 2Hrs Failed 5/6/2024 05/06/2024
David Drake ((253) 864-4171)
Fire Sprinkler
Carried Forward
05/08/2024
Good morning, There are multiple fire sprinkler heads that have obstructions in these rooms. In order not to derail this project I need the fire sprinkler designer to come out onsite and determine how to make this system code compliant with the amount of obstructions created. The wire trays along with wiring are not yet complete and will add another layer of obstructions to this issue once installed. If there is a code compliant path that all these obstructions are allowed, please provide a fully detailed report from your company stating code sections, exemptions, alternative methods, dimensions, or whatever you feel makes this code compliant to me. Please make it PDF attached in an email. At the end of this project we are requiring the FPE (Fire Protection Engineer of record) to complete a close out report stating everything that was addressed is code compliant. This possibly could be a huge derailment at the end. Leonard, I've attached you to this email in hopes you can help with a code path, or fixes to move forward.

Fire Sprinkler Partial Cover
Outstanding
05/08/2024
If there are no changes per the cover inspection corrections this Hydro will be approved as is. If changes are made to the piping, a new Hydro will be required.

Hydrostatic Test 200Lbs 2Hrs Failed 5/6/2024 5/6/2024 05/06/2024
David Drake ((253) 864-4171)
Fire Sprinkler
Carried Forward
05/08/2024
Good morning, There are multiple fire sprinkler heads that have obstructions in these rooms. In order not to derail this project I need the fire sprinkler designer to come out onsite and determine how to make this system code compliant with the amount of obstructions created. The wire trays along with wiring are not yet complete and will add another layer of obstructions to this issue once installed. If there is a code compliant path that all these obstructions are allowed, please provide a fully detailed report from your company stating code sections, exemptions, alternative methods, dimensions, or whatever you feel makes this code compliant to me. Please make it PDF attached in an email. At the end of this project we are requiring the FPE (Fire Protection Engineer of record) to complete a close out report stating everything that was addressed is code compliant. This possibly could be a huge derailment at the end. Leonard, I've attached you to this email in hopes you can help with a code path, or fixes to move forward.

Conditions

Condition Status Department Category Expiration Date Due Date
Fire Sprinkler System (New) Conditions Open Standard Conditions
: • Provide plans and permit on site for inspection. • Cover and final inspections are required. • Fire watch is required when sprinkler system is out of service in existing buildings. • Contractor required at all inspections. • Hydro test will be required on all new and existing buildings. Appointment required. • Hydro test, two inspections will be required 2hrs apart. Call to schedule times. Am/pm is not guaranteed without appointment. • Fire pumps will be required to be tested and witnessed by inspector. • Tool kit required at time of final. • NFPA placards required. • In existing buildings all upright fire sprinklers to remain, do not remove. • In existing buildings all required service and maintenance to be updated prior to inspection. • Due to unforeseeable construction design, all head locations to be field verified for compliance. Schedule your inspection online through the city of puyallup online permit system. This is a request for inspection only. A date and time will be selected by Inspector depending on availability. Email morning of inspection between 7am – 8am for scheduled date and time. Fire Inspections are Monday – Thursday there will be no inspections on Fridays. For larger system please make an appointment prior to scheduling first. David Drake ddrake@puyallupwa.gov

Related Permit & Planning Applications

Reference Number Status Type
PRFO20231761 Permit(s) Issued Foundation Only
PRFO20240140 Permit(s) Issued Foundation Only
PRCCP20240183 In Plan Check Civil Construction Permit
PRFO20240187 Permit(s) Issued Foundation Only
PRMH20240272 Permit(s) Issued Mechanical - COMMERCIAL ONLY
PRCTI20240275 Permit(s) Issued Commercial - Tenant Improvement/Remodel
PRCTI20240333 Permit(s) Issued Commercial - Tenant Improvement/Remodel
PRCTI20240438 Permit(s) Issued Commercial - Tenant Improvement/Remodel
PRCTI20240560 Ready for Issuance Commercial - Tenant Improvement/Remodel
PRFO20240573 In Plan Check Foundation Only
PRMH20240593 Permit(s) Issued Mechanical - COMMERCIAL ONLY
PRCNC20240601 In Plan Check Commercial - New Construction
PRFA20240642 Permit(s) Issued Fire Alarms
PRCNC20240647 In Plan Check Commercial - New Construction
PRFN20240667 Returned for Correction Fence
PLPRE20230121 File Closed Pre-Application
PLSSP20240018 File Closed SEPA Standalone

Documents & Images

Date Uploaded File Type Name
04/09/2024 Plans FLOOR PLAN
04/30/2024 Plans CUT SHEETS (Stamped)
04/09/2024 Plans SEISMIC CALCS
04/30/2024 Plans SPRINKLER PLANS (Stamped)
04/30/2024 Form signed Fire Code Permit Application 0821_202108241006411506 (Flattened)
04/09/2024 Plans HYDRAULIC CALCS
04/09/2024 Receipt Receipt for transaction:2024-000702
04/16/2024 Receipt Receipt for transaction:2024-000773
05/01/2024 Letter Permit - Detailed
05/01/2024 Receipt Receipt for transaction:2024-000890


Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.