CITY OF PUYALLUP PERMITTING PORTAL
Permit Application Status
PRCTI20240333
In order to request inspections, you need to be signed in.
Paid Fees | Amount | Paid | Owing | Date Paid |
---|---|---|---|---|
Fire Review Fee (Commercial Building) | $265.00 | $265.00 | Paid | 03/20/2024 |
Building Permit Fee | $853.75 | $853.75 | Paid | 03/20/2024 |
Building Plan Review Fee | $554.94 | $554.94 | Paid | 03/04/2024 |
WA State Building Code Council Fee (Commercial) | $25.00 | $25.00 | Paid | 03/20/2024 |
Inspection Fee - Outside Of Business Hours | $540.00 | $540.00 | Paid | 04/05/2024 |
Inspection Fee - Outside Of Business Hours | $540.00 | $540.00 | Paid | 04/11/2024 |
Inspection Fee - Outside Of Business Hours | $540.00 | $540.00 | Paid | 04/11/2024 |
Inspection Fee - Outside Of Business Hours | $540.00 | $540.00 | Paid | 04/11/2024 |
Inspection Fee - Outside Of Business Hours | $540.00 | $540.00 | Paid | 04/11/2024 |
Outstanding Fees | Amount | Paid | Owing | Date Paid |
No outstanding fees. | ||||
Totals: | $4,398.69 | $4,398.69 | $0.00 |
Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.
$0.00
Inspection | Outcome | Requested | Scheduled | Date Inspected |
---|---|---|---|---|
Comment Engineering Div Inspection | Pending | |||
Footing/Setback Inspection | Pending | |||
Shannon King ((253) 840-6684) | ||||
Foundation/Rebar Inspection | Pending | |||
Shannon King ((253) 840-6684) | ||||
Slab/Insulation Inspection | Pending | |||
Shannon King ((253) 840-6684) | ||||
Roof Sheathing Inspection | Pending | |||
Shannon King ((253) 840-6684) | ||||
Shear Wall Inspection | Pending | |||
Shannon King ((253) 840-6684) | ||||
Exit Lighting Test Inspection | Pending | |||
David Drake ((253) 864-4171) | ||||
Hydronic Piping Inspection | Pending | |||
Shannon King ((253) 840-6684) | ||||
Refrigeration Line Test Inspection | Pending | |||
Shannon King ((253) 840-6684) | ||||
Exhaust Hood Inspection | Pending | |||
Shannon King ((253) 840-6684) | ||||
Light Test For Grease Duct Inspection | Pending | |||
Shannon King ((253) 840-6684) | ||||
Exhaust/Vent Fans Inspection | Pending | |||
Shannon King ((253) 840-6684) | ||||
Medical Gas Inspection | Pending | |||
Shannon King ((253) 840-6684) | ||||
Fire Or Smoke Damper Inspection | Pending | |||
David Drake ((253) 864-4171) | ||||
Hydrostatic Test 200Lbs 2Hrs | Pending | |||
David Drake ((253) 864-4171) | ||||
Emergency Radio Test Review Inspection | Pending | |||
David Drake ((253) 864-4171) | ||||
Engineering Final Inspection | Pending | |||
Fire Final Inspection | Pending | |||
David Drake ((253) 864-4171) | ||||
Building Final Inspection | Pending | |||
Shannon King ((253) 840-6684) | ||||
Comment Building Div Inspection | Pending | |||
Shannon King ((253) 840-6684) | ||||
Firewall/Firestop Inspection | Pending | |||
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Outstanding
04/09/2024
1 ; complete fire caulk at head of wall in battery room as discussed with contractor.
|
||||
Ceiling Grid/T-Bar Inspection | Pending | |||
Shannon King ((253) 840-6684) | ||||
Frame Inspection | Pending | |||
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Outstanding
01/15/2025
1. framing of opening for electrical at battery room approved
|
||||
Energy (Insulation) Inspection | Pending | |||
Shannon King ((253) 840-6684) | ||||
Wallboard / Drywall Inspection | Pending | |||
Shannon King ((253) 840-6684) | ||||
Frame Inspection | Failed | 3/28/2024 | 3/28/2024 | 03/28/2024 |
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Carried Forward
03/28/2024
1 ; inspection of battery room only.
2 ; provide special inspection approval of welding prior to next inspection.
3 ; provide engineers fix or approval of titen hd anchor installed at angle.
4 ; complete all framing and hardware install as per city approved plans as discussed with contractor.
not ready
|
||||
Combination Frame And Rough In Inspection | Not Ready | 3/29/2024 | 3/29/2024 | 03/29/2024 |
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Carried Forward
03/29/2024
1 ; cancel per contractor - not ready
|
||||
Wallboard / Drywall Inspection | Not Ready | 3/29/2024 | 3/29/2024 | 03/29/2024 |
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Carried Forward
03/29/2024
1 ; cancel per contractor - not ready
|
||||
Planning Final Inspection | VOID | 3/29/2024 | 04/01/2024 | |
Chris Beale ((253) 841-5418) | ||||
Frame Inspection | Failed | 4/2/2024 | 4/2/2024 | 04/02/2024 |
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Carried Forward
04/02/2024
1 ; inspection of battery room only.
2 ; provide special inspection approval of welding prior to next inspection.
3 ; provide engineers fix or approval of titen hd anchor installed at angle.
4 ; complete all framing and hardware install as per city approved plans as discussed with contractor.
not ready
|
||||
Other/Miscellaneous
Carried Forward
04/02/2024
1 ; provide engineers fix or approval for welding performed without periodic special inspection.
2 ; complete titen hd anchors at 3 locations as discussed with contractor at battery room.
|
||||
Comment Building Div Inspection | Not Ready | 4/3/2024 | 4/3/2024 | 04/03/2024 |
Shannon King ((253) 840-6684) | ||||
Combination Frame And Rough In Inspection | Partial Pass | 4/3/2024 | 4/3/2024 | 04/03/2024 |
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Resolved
04/03/2024
1 ; cancel per contractor - not ready
|
||||
Wallboard / Drywall Inspection | Partial Pass | 4/3/2024 | 4/3/2024 | 04/03/2024 |
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Carried Forward
04/03/2024
1 ; cancel per contractor - not ready
|
||||
Frame Inspection | Not Ready | 4/4/2024 | 4/4/2024 | 04/04/2024 |
Kevin Spruell ((253) 841-5590) | ||||
Other/Miscellaneous
Carried Forward
04/04/2024
1 ; inspection of battery room only.
2 ; provide special inspection approval of welding prior to next inspection.
3 ; provide engineers fix or approval of titen hd anchor installed at angle.
4 ; complete all framing and hardware install as per city approved plans as discussed with contractor.
not ready
|
||||
Other/Miscellaneous
Carried Forward
04/04/2024
1 ; provide engineers fix or approval for welding performed without periodic special inspection.
2 ; complete titen hd anchors at 3 locations as discussed with contractor at battery room.
|
||||
Energy (Insulation) Inspection | Partial Pass | 4/5/2024 | 4/5/2024 | 04/05/2024 |
Shannon King ((253) 840-6684) | ||||
Wallboard / Drywall Inspection | Not Ready | 4/5/2024 | 4/5/2024 | 04/05/2024 |
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Carried Forward
04/05/2024
1 ; cancel per contractor - not ready
|
||||
Wallboard / Drywall Inspection | Partial Pass | 4/8/2024 | 4/6/2024 | 04/06/2024 |
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Carried Forward
04/06/2024
1 ; cancel per contractor - not ready
|
||||
Firewall/Firestop Inspection | Failed | 4/9/2024 | 4/9/2024 | 04/09/2024 |
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Carried Forward
04/09/2024
1 ; complete fire caulk at head of wall in battery room as discussed with contractor.
|
||||
Wallboard / Drywall Inspection | Not Ready | 4/9/2024 | 4/9/2024 | 04/09/2024 |
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Carried Forward
04/09/2024
1 ; cancel per contractor - not ready
|
||||
Wallboard / Drywall Inspection | Partial Pass | 4/11/2024 | 4/11/2024 | 04/11/2024 |
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Resolved
04/11/2024
1 ; cancel per contractor - not ready
|
||||
Wallboard / Drywall Inspection | Failed | 4/12/2024 | 04/12/2024 | |
Kevin Spruell ((253) 841-5590) | ||||
Other/Miscellaneous
Carried Forward
04/12/2024
THIS WAS AN AFTER HOURS INSPECTION 4/10/2024
1.complete first layer of ceiling in battery room per UL listing as discussed with contractor
|
||||
Wallboard / Drywall Inspection | Partial Pass | 4/12/2024 | 04/12/2024 | |
Kevin Spruell ((253) 841-5590) | ||||
Other/Miscellaneous
Resolved
04/12/2024
THIS WAS AN AFTER HOURS INSPECTION 4/10/2024
1.complete first layer of ceiling in battery room per UL listing as discussed with contractor
|
||||
Other/Miscellaneous
Carried Forward
04/12/2024
THIS WAS AN AFTER HOURS INSPECTION ON 4/11/2024
1. second layer of ceiling in battery room approved
2. first layer of drywall at walls around doors approved
|
||||
Frame Inspection | Partial Pass | 4/12/2024 | 04/15/2024 | |
Kevin Spruell ((253) 841-5590) | ||||
Other/Miscellaneous
Resolved
04/15/2024
1 ; inspection of battery room only.
2 ; provide special inspection approval of welding prior to next inspection.
3 ; provide engineers fix or approval of titen hd anchor installed at angle.
4 ; complete all framing and hardware install as per city approved plans as discussed with contractor.
not ready
|
||||
Other/Miscellaneous
Resolved
04/15/2024
1 ; provide engineers fix or approval for welding performed without periodic special inspection.
2 ; complete titen hd anchors at 3 locations as discussed with contractor at battery room.
|
||||
Other/Miscellaneous
Carried Forward
04/15/2024
THIS INSPECTION WAS ON 4/11/2024
1.door install and framing around doors at battery and UPS room approved
|
||||
Wallboard / Drywall Inspection | Partial Pass | 4/12/2024 | 04/15/2024 | |
Kevin Spruell ((253) 841-5590) | ||||
Other/Miscellaneous
Resolved
04/15/2024
THIS WAS AN AFTER HOURS INSPECTION ON 4/11/2024
1. second layer of ceiling in battery room approved
2. first layer of drywall at walls around doors approved
|
||||
Other/Miscellaneous
Carried Forward
04/15/2024
THIS WAS AN AFTER HOURS INSPECTION ON 4/12/2024
1.second layer of drywall around doors at battery and UPS rooms approved
2. third layer and hat channel on ceiling of battery room approved
|
||||
Wallboard / Drywall Inspection | Partial Pass | 4/15/2024 | 04/15/2024 | |
Kevin Spruell ((253) 841-5590) | ||||
Other/Miscellaneous
Resolved
04/15/2024
THIS WAS AN AFTER HOURS INSPECTION ON 4/12/2024
1.second layer of drywall around doors at battery and UPS rooms approved
2. third layer and hat channel on ceiling of battery room approved
|
||||
Other/Miscellaneous
Carried Forward
04/15/2024
THIS WAS AN AFTER HOURS INSPECTION ON 4/13/2024
1. 4 layer of drywall on ceiling in battery room approved ok to tape
|
||||
Frame Inspection | Partial Pass | 4/16/2024 | 4/16/2024 | 04/16/2024 |
Kevin Spruell ((253) 841-5590) | ||||
Other/Miscellaneous
Resolved
04/16/2024
THIS INSPECTION WAS ON 4/11/2024
1.door install and framing around doors at battery and UPS room approved
|
||||
Other/Miscellaneous
Carried Forward
04/16/2024
1. framing of opening for electrical at battery room approved
|
||||
Ceiling Grid/T-Bar Inspection | Partial Pass | 5/7/2024 | 5/7/2024 | 05/07/2024 |
Shannon King ((253) 840-6684) | ||||
Wallboard / Drywall Inspection | Not Ready | 8/15/2024 | 8/15/2024 | 08/15/2024 |
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Resolved
08/15/2024
THIS WAS AN AFTER HOURS INSPECTION ON 4/13/2024
1. 4 layer of drywall on ceiling in battery room approved ok to tape
|
||||
Frame Inspection | Partial Pass | 8/16/2024 | 8/16/2024 | 08/16/2024 |
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Carried Forward
08/16/2024
1. framing of opening for electrical at battery room approved
|
||||
Frame Inspection | Not Ready | 1/13/2025 | 1/13/2025 | 01/13/2025 |
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Carried Forward
01/13/2025
1. framing of opening for electrical at battery room approved
|
||||
Frame Inspection | Partial Pass | 1/15/2025 | 1/15/2025 | 01/15/2025 |
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Carried Forward
01/15/2025
1. framing of opening for electrical at battery room approved
|
||||
Energy (Insulation) Inspection | Partial Pass | 1/16/2025 | 1/16/2025 | 01/16/2025 |
Shannon King ((253) 840-6684) | ||||
Wallboard / Drywall Inspection | Partial Pass | 1/21/2025 | 1/21/2025 | 01/21/2025 |
Shannon King ((253) 840-6684) |
Condition | Status | Department | Category | Expiration Date | Due Date |
---|---|---|---|---|---|
Building Permit Standard Conditions | Open | Building Division | Standard Conditions | ||
:
* Final approval by the Building Official is required prior to use or occupancy.* Work shall not proceed until the inspector has approved the stages of construction.* Surface storm water shall be diverted from the building site and shall not drain onto adjacent properties.* I hereby acknowledge that I have read this Permit/Application, that the information given is correct; that I am the owner or the duly authorized agent of the owner; that plans submitted herewith are in compliance with all applicable city, county and state laws and that all construction will proceed in accordance with said laws. This permit shall expire if work is not commenced with 180 days or if the work is suspended for a period of 180 days. Permits expire two years from issuance. * By leaving the contractor information section blank, I hereby certify further that contractors (general or subcontractors) will not be hired to perform any work in association with this permit. I also certify that if I do choose to hire a contractor (general or subcontractor) I will only hire those contractors that are licensed by the State of Washington. If you are a property owner, contractor or permittee and you are paying for someone to perform the work, they must have a valid contractor registration and the person(s) installing plumbing inside a structure must meet the plumbing certification requirements. If you have any questions regarding these regulations, you may contact the Washington State Department of Labor and Industries or you can find more information on-line at: http://www.lni.wa.gov/TradesLicensing/Contractors/HireCon/default.asp
|
|||||
Fire Review Conditions | Open | Standard Conditions | |||
:
• Comply with 2018 IFC and 2018 IBC
• Total coverage required in the city of puyallup
• L&I Final required prior to Fire Final
• Exit lighting test required, contractor to provide light meter
• Separate permits required for Fire Alarm and Fire Sprinkler
• RTU’S will be required to be tested for shut down
• Smoke and Fire dampeners will be tested with Fire Alarm. Access doors are required for maintenance and visual inspection.
• Fire extinguishers required per code
• A Knox box is required at the front entry on the exterior of the building if equipped with a Fire Alarm System or Fire Sprinkler System.
• PIV must have a Knox lock or approved lock with an extra key provided in Knox box
• Existing buildings will need to contact central pierce fire & rescue and update the key in the Knox box
• All above items to be completed prior to fire final. Fire final required before building final
Schedule your inspection online through the city of puyallup online permit system. This is a request for inspection only. A date and time will be selected by Inspector depending on availability. Email morning of inspection between 7am – 8am for scheduled date and time. Fire Inspections are Monday – Thursday there will be no inspections on Fridays. David Drake ddrake@puyallupwa.gov
|
|||||
Contaminated Site Remediation | Open | Engineering Division | Standard Conditions | ||
:
The subject property has been classified as a contaminated site by the Tacoma Pierce County Health Department (TPCHD) and must be remediated per Washington Administrative Code Title 173. It is the applicant’s responsibility to coordinate cleanup with TPCHD. Visit https://www.tpchd.org/healthy-places/contaminated-property-cleanup for more information. The applicant shall request a remediation status report from TPCHD by emailing UST@tpchd.org. Provide a copy of the status report to the City.
|
Reference Number | Status | Type |
---|---|---|
PRFO20231761 | Closed | Foundation Only |
PRFO20240140 | Permit(s) Issued | Foundation Only |
PRCCP20240183 | Permit(s) Issued | Civil Construction Permit |
PRFO20240187 | Permit(s) Issued | Foundation Only |
PRMH20240272 | Permit(s) Issued | Mechanical - COMMERCIAL ONLY |
PRCTI20240275 | Permit(s) Issued | Commercial - Tenant Improvement/Remodel |
PRCTI20240438 | Permit(s) Issued | Commercial - Tenant Improvement/Remodel |
PRCTI20240560 | Permit(s) Issued | Commercial - Tenant Improvement/Remodel |
PRFO20240573 | Permit(s) Issued | Foundation Only |
PRMH20240593 | Permit(s) Issued | Mechanical - COMMERCIAL ONLY |
PRFS20240598 | Closed | Fire Sprinklers |
PRCNC20240601 | Permit(s) Issued | Commercial - New Construction |
PRFA20240642 | Closed | Fire Alarms |
PRCNC20240647 | Permit(s) Issued | Commercial - New Construction |
PRFN20240667 | Permit(s) Issued | Fence |
PRCTI20240782 | Permit(s) Issued | Commercial - Tenant Improvement/Remodel |
PRCTI20240784 | Permit(s) Issued | Commercial - Tenant Improvement/Remodel |
PRFA20240822 | Closed | Fire Alarms |
PRMH20240831 | Permit(s) Issued | Mechanical - COMMERCIAL ONLY |
PRCTI20240892 | Permit(s) Issued | Commercial - Tenant Improvement/Remodel |
PRFA20241312 | Closed | Fire Alarms |
PRCTI20241387 | Permit(s) Issued | Commercial - Tenant Improvement/Remodel |
PRFA20241456 | Closed | Fire Alarms |
PRFA20241475 | Permit(s) Issued | Fire Alarms |
PRFS20241490 | Closed | Fire Sprinklers |
PRCNC20241741 | Ready for Issuance | Commercial - New Construction |
PRMH20241875 | Permit(s) Issued | Mechanical - COMMERCIAL ONLY |
PRRWF20241913 | Returned for Correction | Retaining Wall |
PRCTI20242004 | Permit(s) Issued | Commercial - Tenant Improvement/Remodel |
PRCTI20250032 | Returned for Correction | Commercial - Tenant Improvement/Remodel |
PRFA20250095 | In Plan Check | Fire Alarms |
PLPRE20230121 | File Closed | Pre-Application |
PLSSP20240018 | File Closed | SEPA Standalone |
Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.