CITY OF PUYALLUP PERMITTING PORTAL

Permit Application Status

PRCTI20240333


In order to request inspections, you need to be signed in.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRCTI20240333
Commercial - Tenant Improvement/Remodel
Permit(s) Issued
BCC PUYALLUP LLC
Alteration/Remodel
Interior tenant improvements to construct new UPS ROOM of 2,223 s.f. and new BATTERY ROOM of 1,474 s.f. - CENTERIS VOLTAGE PARK
03/01/2024
03/20/2024
11/03/2024

Locations

Reviews

Documents Returned For Corrections

Review Type Outcome Est. Completion Date Completed
Building Review Approved 03/25/2024 03/20/2024
Fire Review Approved 03/25/2024 03/19/2024
Planning Review Approved 04/03/2024 03/13/2024
Engineering Review Approved 04/03/2024 03/11/2024

Fees

Paid Fees Amount Paid Owing Date Paid
Fire Review Fee (Commercial Building) $265.00 $265.00 Paid 03/20/2024
Building Permit Fee $853.75 $853.75 Paid 03/20/2024
Building Plan Review Fee $554.94 $554.94 Paid 03/04/2024
WA State Building Code Council Fee (Commercial) $25.00 $25.00 Paid 03/20/2024
Inspection Fee - Outside Of Business Hours $540.00 $540.00 Paid 04/05/2024
Inspection Fee - Outside Of Business Hours $540.00 $540.00 Paid 04/11/2024
Inspection Fee - Outside Of Business Hours $540.00 $540.00 Paid 04/11/2024
Inspection Fee - Outside Of Business Hours $540.00 $540.00 Paid 04/11/2024
Inspection Fee - Outside Of Business Hours $540.00 $540.00 Paid 04/11/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Comment Engineering Div Inspection Pending
Footing/Setback Inspection Pending
Shannon King ((253) 840-6684)
Foundation/Rebar Inspection Pending
Shannon King ((253) 840-6684)
Slab/Insulation Inspection Pending
Shannon King ((253) 840-6684)
Roof Sheathing Inspection Pending
Shannon King ((253) 840-6684)
Shear Wall Inspection Pending
Shannon King ((253) 840-6684)
Exit Lighting Test Inspection Pending
David Drake ((253) 864-4171)
Hydronic Piping Inspection Pending
Shannon King ((253) 840-6684)
Refrigeration Line Test Inspection Pending
Shannon King ((253) 840-6684)
Exhaust Hood Inspection Pending
Shannon King ((253) 840-6684)
Light Test For Grease Duct Inspection Pending
Shannon King ((253) 840-6684)
Exhaust/Vent Fans Inspection Pending
Shannon King ((253) 840-6684)
Medical Gas Inspection Pending
Shannon King ((253) 840-6684)
Fire Or Smoke Damper Inspection Pending
David Drake ((253) 864-4171)
Hydrostatic Test 200Lbs 2Hrs Pending
David Drake ((253) 864-4171)
Emergency Radio Test Review Inspection Pending
David Drake ((253) 864-4171)
Engineering Final Inspection Pending
Fire Final Inspection Pending
David Drake ((253) 864-4171)
Building Final Inspection Pending
Shannon King ((253) 840-6684)
Comment Building Div Inspection Pending
Shannon King ((253) 840-6684)
Energy (Insulation) Inspection Pending
Shannon King ((253) 840-6684)
Firewall/Firestop Inspection Pending
Shannon King ((253) 840-6684)
Other/Miscellaneous
Outstanding
04/09/2024
1 ; complete fire caulk at head of wall in battery room as discussed with contractor.

Wallboard / Drywall Inspection Pending
Shannon King ((253) 840-6684)
Other/Miscellaneous
Outstanding
04/15/2024
THIS WAS AN AFTER HOURS INSPECTION ON 4/13/2024 1. 4 layer of drywall on ceiling in battery room approved ok to tape

Frame Inspection Pending
Shannon King ((253) 840-6684)
Other/Miscellaneous
Outstanding
04/16/2024
1. framing of opening for electrical at battery room approved

Ceiling Grid/T-Bar Inspection Pending
Shannon King ((253) 840-6684)
Frame Inspection Failed 3/28/2024 3/28/2024 03/28/2024
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
03/28/2024
1 ; inspection of battery room only. 2 ; provide special inspection approval of welding prior to next inspection. 3 ; provide engineers fix or approval of titen hd anchor installed at angle. 4 ; complete all framing and hardware install as per city approved plans as discussed with contractor. not ready

Combination Frame And Rough In Inspection Not Ready 3/29/2024 3/29/2024 03/29/2024
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
03/29/2024
1 ; cancel per contractor - not ready

Wallboard / Drywall Inspection Not Ready 3/29/2024 3/29/2024 03/29/2024
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
03/29/2024
1 ; cancel per contractor - not ready

Planning Final Inspection VOID 3/29/2024 04/01/2024
Chris Beale ((253) 841-5418)
Frame Inspection Failed 4/2/2024 4/2/2024 04/02/2024
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
04/02/2024
1 ; inspection of battery room only. 2 ; provide special inspection approval of welding prior to next inspection. 3 ; provide engineers fix or approval of titen hd anchor installed at angle. 4 ; complete all framing and hardware install as per city approved plans as discussed with contractor. not ready

Other/Miscellaneous
Carried Forward
04/02/2024
1 ; provide engineers fix or approval for welding performed without periodic special inspection. 2 ; complete titen hd anchors at 3 locations as discussed with contractor at battery room.

Comment Building Div Inspection Not Ready 4/3/2024 4/3/2024 04/03/2024
Shannon King ((253) 840-6684)
Combination Frame And Rough In Inspection Partial Pass 4/3/2024 4/3/2024 04/03/2024
Shannon King ((253) 840-6684)
Other/Miscellaneous
Resolved
04/03/2024
1 ; cancel per contractor - not ready

Wallboard / Drywall Inspection Partial Pass 4/3/2024 4/3/2024 04/03/2024
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
04/03/2024
1 ; cancel per contractor - not ready

Frame Inspection Not Ready 4/4/2024 4/4/2024 04/04/2024
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Carried Forward
04/04/2024
1 ; inspection of battery room only. 2 ; provide special inspection approval of welding prior to next inspection. 3 ; provide engineers fix or approval of titen hd anchor installed at angle. 4 ; complete all framing and hardware install as per city approved plans as discussed with contractor. not ready

Other/Miscellaneous
Carried Forward
04/04/2024
1 ; provide engineers fix or approval for welding performed without periodic special inspection. 2 ; complete titen hd anchors at 3 locations as discussed with contractor at battery room.

Energy (Insulation) Inspection Partial Pass 4/5/2024 4/5/2024 04/05/2024
Shannon King ((253) 840-6684)
Wallboard / Drywall Inspection Not Ready 4/5/2024 4/5/2024 04/05/2024
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
04/05/2024
1 ; cancel per contractor - not ready

Wallboard / Drywall Inspection Partial Pass 4/8/2024 4/6/2024 04/06/2024
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
04/06/2024
1 ; cancel per contractor - not ready

Firewall/Firestop Inspection Failed 4/9/2024 4/9/2024 04/09/2024
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
04/09/2024
1 ; complete fire caulk at head of wall in battery room as discussed with contractor.

Wallboard / Drywall Inspection Not Ready 4/9/2024 4/9/2024 04/09/2024
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
04/09/2024
1 ; cancel per contractor - not ready

Wallboard / Drywall Inspection Partial Pass 4/11/2024 4/11/2024 04/11/2024
Shannon King ((253) 840-6684)
Other/Miscellaneous
Resolved
04/11/2024
1 ; cancel per contractor - not ready

Wallboard / Drywall Inspection Failed 4/12/2024 04/12/2024
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Carried Forward
04/12/2024
THIS WAS AN AFTER HOURS INSPECTION 4/10/2024 1.complete first layer of ceiling in battery room per UL listing as discussed with contractor

Wallboard / Drywall Inspection Partial Pass 4/12/2024 04/12/2024
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Resolved
04/12/2024
THIS WAS AN AFTER HOURS INSPECTION 4/10/2024 1.complete first layer of ceiling in battery room per UL listing as discussed with contractor

Other/Miscellaneous
Carried Forward
04/12/2024
THIS WAS AN AFTER HOURS INSPECTION ON 4/11/2024 1. second layer of ceiling in battery room approved 2. first layer of drywall at walls around doors approved

Frame Inspection Partial Pass 4/12/2024 04/15/2024
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Resolved
04/15/2024
1 ; inspection of battery room only. 2 ; provide special inspection approval of welding prior to next inspection. 3 ; provide engineers fix or approval of titen hd anchor installed at angle. 4 ; complete all framing and hardware install as per city approved plans as discussed with contractor. not ready

Other/Miscellaneous
Resolved
04/15/2024
1 ; provide engineers fix or approval for welding performed without periodic special inspection. 2 ; complete titen hd anchors at 3 locations as discussed with contractor at battery room.

Other/Miscellaneous
Carried Forward
04/15/2024
THIS INSPECTION WAS ON 4/11/2024 1.door install and framing around doors at battery and UPS room approved

Wallboard / Drywall Inspection Partial Pass 4/12/2024 04/15/2024
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Resolved
04/15/2024
THIS WAS AN AFTER HOURS INSPECTION ON 4/11/2024 1. second layer of ceiling in battery room approved 2. first layer of drywall at walls around doors approved

Other/Miscellaneous
Carried Forward
04/15/2024
THIS WAS AN AFTER HOURS INSPECTION ON 4/12/2024 1.second layer of drywall around doors at battery and UPS rooms approved 2. third layer and hat channel on ceiling of battery room approved

Wallboard / Drywall Inspection Partial Pass 4/15/2024 04/15/2024
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Resolved
04/15/2024
THIS WAS AN AFTER HOURS INSPECTION ON 4/12/2024 1.second layer of drywall around doors at battery and UPS rooms approved 2. third layer and hat channel on ceiling of battery room approved

Other/Miscellaneous
Carried Forward
04/15/2024
THIS WAS AN AFTER HOURS INSPECTION ON 4/13/2024 1. 4 layer of drywall on ceiling in battery room approved ok to tape

Frame Inspection Partial Pass 4/16/2024 4/16/2024 04/16/2024
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Resolved
04/16/2024
THIS INSPECTION WAS ON 4/11/2024 1.door install and framing around doors at battery and UPS room approved

Other/Miscellaneous
Carried Forward
04/16/2024
1. framing of opening for electrical at battery room approved

Ceiling Grid/T-Bar Inspection Partial Pass 5/7/2024 5/7/2024 05/07/2024
Shannon King ((253) 840-6684)

Conditions

Condition Status Department Category Expiration Date Due Date
Building Permit Standard Conditions Open Building Division Standard Conditions
: * Final approval by the Building Official is required prior to use or occupancy.* Work shall not proceed until the inspector has approved the stages of construction.* Surface storm water shall be diverted from the building site and shall not drain onto adjacent properties.* I hereby acknowledge that I have read this Permit/Application, that the information given is correct; that I am the owner or the duly authorized agent of the owner; that plans submitted herewith are in compliance with all applicable city, county and state laws and that all construction will proceed in accordance with said laws. This permit shall expire if work is not commenced with 180 days or if the work is suspended for a period of 180 days. Permits expire two years from issuance. * By leaving the contractor information section blank, I hereby certify further that contractors (general or subcontractors) will not be hired to perform any work in association with this permit. I also certify that if I do choose to hire a contractor (general or subcontractor) I will only hire those contractors that are licensed by the State of Washington. If you are a property owner, contractor or permittee and you are paying for someone to perform the work, they must have a valid contractor registration and the person(s) installing plumbing inside a structure must meet the plumbing certification requirements. If you have any questions regarding these regulations, you may contact the Washington State Department of Labor and Industries or you can find more information on-line at: http://www.lni.wa.gov/TradesLicensing/Contractors/HireCon/default.asp
Fire Review Conditions Open Standard Conditions
: • Comply with 2018 IFC and 2018 IBC • Total coverage required in the city of puyallup • L&I Final required prior to Fire Final • Exit lighting test required, contractor to provide light meter • Separate permits required for Fire Alarm and Fire Sprinkler • RTU’S will be required to be tested for shut down • Smoke and Fire dampeners will be tested with Fire Alarm. Access doors are required for maintenance and visual inspection. • Fire extinguishers required per code • A Knox box is required at the front entry on the exterior of the building if equipped with a Fire Alarm System or Fire Sprinkler System. • PIV must have a Knox lock or approved lock with an extra key provided in Knox box • Existing buildings will need to contact central pierce fire & rescue and update the key in the Knox box • All above items to be completed prior to fire final. Fire final required before building final Schedule your inspection online through the city of puyallup online permit system. This is a request for inspection only. A date and time will be selected by Inspector depending on availability. Email morning of inspection between 7am – 8am for scheduled date and time. Fire Inspections are Monday – Thursday there will be no inspections on Fridays. David Drake ddrake@puyallupwa.gov
Contaminated Site Remediation Open Engineering Division Standard Conditions
: The subject property has been classified as a contaminated site by the Tacoma Pierce County Health Department (TPCHD) and must be remediated per Washington Administrative Code Title 173. It is the applicant’s responsibility to coordinate cleanup with TPCHD. Visit https://www.tpchd.org/healthy-places/contaminated-property-cleanup for more information. The applicant shall request a remediation status report from TPCHD by emailing UST@tpchd.org. Provide a copy of the status report to the City.

Related Permit & Planning Applications

Reference Number Status Type
PRFO20231761 Permit(s) Issued Foundation Only
PRFO20240140 Permit(s) Issued Foundation Only
PRCCP20240183 In Plan Check Civil Construction Permit
PRFO20240187 Permit(s) Issued Foundation Only
PRMH20240272 Permit(s) Issued Mechanical - COMMERCIAL ONLY
PRCTI20240275 Permit(s) Issued Commercial - Tenant Improvement/Remodel
PRCTI20240438 Permit(s) Issued Commercial - Tenant Improvement/Remodel
PRCTI20240560 Ready for Issuance Commercial - Tenant Improvement/Remodel
PRFO20240573 In Plan Check Foundation Only
PRMH20240593 Permit(s) Issued Mechanical - COMMERCIAL ONLY
PRFS20240598 Permit(s) Issued Fire Sprinklers
PRCTI20240601 In Plan Check Commercial - Tenant Improvement/Remodel
PRFA20240642 Permit(s) Issued Fire Alarms
PRCNC20240647 In Plan Check Commercial - New Construction
PRFN20240667 Returned for Correction Fence
PLPRE20230121 File Closed Pre-Application
PLSSP20240018 File Closed SEPA Standalone

Documents & Images

Date Uploaded File Type Name
03/20/2024 Report STURCTURAL CALCS (Stamped)
03/20/2024 Plans CONSTRUCTION PLAN SET (Stamped)
03/20/2024 Form APPLICATION FORM TI UPS+Battery Room (Flattened)
03/20/2024 Plans CONSTRUCTION PLAN SET ARCHITECTURAL (Stamped)
03/04/2024 Receipt Receipt for transaction:2024-000401
03/20/2024 Letter Permit - Detailed
03/20/2024 Receipt Receipt for transaction:2024-000560
03/28/2024 Report Inspection Report (Frame Inspection)
03/29/2024 Report Inspection Report (Combination Frame And Rough In Inspection)
03/29/2024 Report Inspection Report (Wallboard / Drywall Inspection)
04/02/2024 Report Inspection Report (Frame Inspection)
04/03/2024 Report Inspection Report (Comment Building Div Inspection)
04/03/2024 Report Inspection Report (Combination Frame And Rough In Inspection)
04/03/2024 Report Inspection Report (Wallboard / Drywall Inspection)
04/04/2024 Report Inspection Report (Frame Inspection)
04/05/2024 Report Inspection Report (Energy (Insulation) Inspection)
04/05/2024 Report Inspection Report (Wallboard / Drywall Inspection)
04/05/2024 Receipt Receipt for transaction:2024-000672
04/06/2024 Report Inspection Report (Wallboard / Drywall Inspection)
04/09/2024 Report Inspection Report (Firewall/Firestop Inspection)
04/09/2024 Report Inspection Report (Wallboard / Drywall Inspection)
04/10/2024 Report Inspection Report (Combination Frame And Rough In Inspection)
04/11/2024 Receipt Receipt for transaction:2024-000735
04/11/2024 Report Inspection Report (Wallboard / Drywall Inspection)
04/12/2024 Report Inspection Report (Wallboard / Drywall Inspection)
04/12/2024 Report Inspection Report (Wallboard / Drywall Inspection)
04/15/2024 Report Inspection Report (Frame Inspection)
04/15/2024 Report Inspection Report (Wallboard / Drywall Inspection)
04/15/2024 Report Inspection Report (Wallboard / Drywall Inspection)
04/16/2024 Report Inspection Report (Frame Inspection)


Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.