CITY OF PUYALLUP PERMITTING PORTAL
Permit Application Status
PRFO20240187
In order to request inspections, you need to be signed in.
Paid Fees | Amount | Paid | Owing | Date Paid |
---|---|---|---|---|
Fire Review Fee (Commercial Building) | $265.00 | $265.00 | Paid | 02/20/2024 |
Building Permit Fee | $1,833.75 | $1,833.75 | Paid | 02/20/2024 |
Building Plan Review Fee | $1,191.94 | $1,191.94 | Paid | 02/06/2024 |
WA State Building Code Council Fee (Commercial) | $25.00 | $25.00 | Paid | 02/20/2024 |
Outstanding Fees | Amount | Paid | Owing | Date Paid |
No outstanding fees. | ||||
Totals: | $3,315.69 | $3,315.69 | $0.00 |
Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.
$0.00
Inspection | Outcome | Requested | Scheduled | Date Inspected |
---|---|---|---|---|
Plumbing Below Slab Inspection | Pending | |||
Shannon King ((253) 840-6684) | ||||
Plumbing Rough In Inspection | Pending | |||
Shannon King ((253) 840-6684) | ||||
Engineering Final Inspection | Pending | |||
Plumbing Final Inspection | Pending | |||
Shannon King ((253) 840-6684) | ||||
Building Final Inspection | Pending | |||
Shannon King ((253) 840-6684) | ||||
Footing/Setback Inspection | Pending | |||
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Outstanding
03/13/2024
1 ; provide min. bar lap at footing of retaining walls with min. 3'' from soil to rebar.
2 ; provide step detail for footing as discussed with contractor.
3 ; provide geo-tech approval for soil bearing of 2,000 psf as required per plans.
|
||||
Slab/Insulation Inspection | Pending | |||
Shannon King ((253) 840-6684) | ||||
Foundation/Rebar Inspection | Pending | |||
Shannon King ((253) 840-6684) | ||||
Foundation/Rebar Inspection | Not Ready | 3/12/2024 | 3/12/2024 | 03/12/2024 |
Shannon King ((253) 840-6684) | ||||
Footing/Setback Inspection | Failed | 3/13/2024 | 3/13/2024 | 03/13/2024 |
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Carried Forward
03/13/2024
1 ; provide min. bar lap at footing of retaining walls with min. 3'' from soil to rebar.
2 ; provide step detail for footing as discussed with contractor.
3 ; provide geo-tech approval for soil bearing of 2,000 psf as required per plans.
|
||||
Foundation/Rebar Inspection | Partial Pass | 3/20/2024 | 3/20/2024 | 03/20/2024 |
Shannon King ((253) 840-6684) | ||||
Foundation/Rebar Inspection | Not Ready | 3/21/2024 | 3/21/2024 | 03/21/2024 |
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Carried Forward
03/21/2024
1 ; complete all rebar and forms with special inspection approval of retaining wall prior to next inspection. ( not ready)
|
||||
Foundation/Rebar Inspection | Partial Pass | 3/22/2024 | 3/22/2024 | 03/22/2024 |
Kevin Spruell ((253) 841-5590) | ||||
Other/Miscellaneous
Resolved
03/22/2024
1 ; complete all rebar and forms with special inspection approval of retaining wall prior to next inspection. ( not ready)
|
||||
Foundation/Rebar Inspection | Partial Pass | 3/27/2024 | 3/27/2024 | 03/27/2024 |
Shannon King ((253) 840-6684) | ||||
Foundation/Rebar Inspection | Partial Pass | 4/4/2024 | 4/4/2024 | 04/04/2024 |
Kevin Spruell ((253) 841-5590) | ||||
Foundation/Rebar Inspection | Failed | 4/8/2024 | 4/8/2024 | 04/08/2024 |
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Carried Forward
04/08/2024
1 ; provide special inspection approval at both generator pads .
2 ; provide min. 3'' from soil to rebar.
3 ; complete all rebar as per city approved plans prior to next inspection.
|
||||
Other/Miscellaneous
Carried Forward
04/08/2024
|
||||
Slab/Insulation Inspection | Failed | 4/9/2024 | 4/9/2024 | 04/09/2024 |
Shannon King ((253) 840-6684) | ||||
Foundation/Rebar Inspection | Partial Pass | 4/12/2024 | 4/12/2024 | 04/12/2024 |
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Resolved
04/12/2024
1 ; provide special inspection approval at both generator pads .
2 ; provide min. 3'' from soil to rebar.
3 ; complete all rebar as per city approved plans prior to next inspection.
|
||||
Other/Miscellaneous
Carried Forward
04/12/2024
|
||||
Foundation/Rebar Inspection | Partial Pass | 4/17/2024 | 4/17/2024 | 04/17/2024 |
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Resolved
04/17/2024
|
||||
Foundation/Rebar Inspection | Partial Pass | 5/15/2024 | 5/15/2024 | 05/15/2024 |
Shannon King ((253) 840-6684) | ||||
Foundation/Rebar Inspection | Partial Pass | 5/22/2024 | 5/22/2024 | 05/22/2024 |
Shannon King ((253) 840-6684) | ||||
Foundation/Rebar Inspection | Partial Pass | 6/12/2024 | 6/12/2024 | 06/12/2024 |
Shannon King ((253) 840-6684) | ||||
Foundation/Rebar Inspection | Partial Pass | 6/21/2024 | 6/21/2024 | 06/21/2024 |
Shannon King ((253) 840-6684) | ||||
Foundation/Rebar Inspection | Partial Pass | 8/14/2024 | 8/14/2024 | 08/14/2024 |
Shannon King ((253) 840-6684) | ||||
Foundation/Rebar Inspection | Partial Pass | 10/30/2024 | 10/30/2024 | 10/30/2024 |
Monty Johnson ((253) 770-3326) | ||||
Other/Miscellaneous
Carried Forward
10/30/2024
progressing with special insp
|
Condition | Status | Department | Category | Expiration Date | Due Date |
---|---|---|---|---|---|
Building Permit Standard Conditions | Open | Building Division | Standard Conditions | ||
:
* Final approval by the Building Official is required prior to use or occupancy.* Work shall not proceed until the inspector has approved the stages of construction.* Surface storm water shall be diverted from the building site and shall not drain onto adjacent properties.* I hereby acknowledge that I have read this Permit/Application, that the information given is correct; that I am the owner or the duly authorized agent of the owner; that plans submitted herewith are in compliance with all applicable city, county and state laws and that all construction will proceed in accordance with said laws. This permit shall expire if work is not commenced with 180 days or if the work is suspended for a period of 180 days. Permits expire two years from issuance. * By leaving the contractor information section blank, I hereby certify further that contractors (general or subcontractors) will not be hired to perform any work in association with this permit. I also certify that if I do choose to hire a contractor (general or subcontractor) I will only hire those contractors that are licensed by the State of Washington. If you are a property owner, contractor or permittee and you are paying for someone to perform the work, they must have a valid contractor registration and the person(s) installing plumbing inside a structure must meet the plumbing certification requirements. If you have any questions regarding these regulations, you may contact the Washington State Department of Labor and Industries or you can find more information on-line at: http://www.lni.wa.gov/TradesLicensing/Contractors/HireCon/default.asp
|
|||||
Fire Review Conditions | Open | Standard Conditions | |||
:
1. INSTALL ADDRESS NUMBERS PER THE FOLLOWING DISTANCES:0-50FOOT SETBACK FROM STREET NUMBERS SHALL BE 6 INCHES IN HEIGHT; 51-100 FEET 12 INCHES IN HEIGHT. ALL NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND. ADDITIONAL NUMBERS MAY BE NEEDED AT DRIVEWAY ENTRANCE IF BUILDING NUMBERS ARE NOT VISIBLE FROM THE STREET. REAR DOORS OF SUITES OR UNITS SHALL ALSO BE LABELED WITH MINIMUM 4 INCH NUMBERS.
2. FIRE HYDRANTS REQUIRED FOR CONSTRUCTION AND FIRE DEPARTMENT ACCESS SHALL BE INSTALLED AND APPROVED BY THE FIRE CODE OFFICIAL PRIOR TO THE STORAGE OR INSTALLATION OF ANY COMBUSTIBLE FRAMING MATERIAL. ACCESS ROADWAY SURFACES SHALL BE DESIGNED TO CITY STANDARDS AND BE DESIGNED TO MAINTAIN THE IMPOSED LOADS OF A 80,000 POUND FIRE APPARATUS. ASPHALT TREATED BASE, ASPHALT OR CONCRETE PAVEMENT CAN BE USED TO PROVIDE THE REQUIRED ALL-WEATHER DRIVING SURFACE.
3. ANY REQUIRED FIRE LANE MARKINGS SHALL BE INSTALLED PRIOR TO FINAL INSPECTION AND PER CITY ORDINANCE.
4. KNOX BOXES, WHEN REQUIRED, SHALL BE INSTALLED USUALLY TO THE RIGHT OF THE MAIN FRONT DOOR AND NO HIGHER THAN 6 FEET OFF OF THE GROUND. ONLY HINGED KNOX BOXES SHALL BE USED. KNOX BOXES AND KEY SWITCHES CAN BE ORDERED ONLINE AT THE "KNOX COMPANY"
5. FIRE EXTINGUISHERS WILL BE REQUIRED PER CHAPTER 9 OF THE INTERNATIONAL FIRE CODE. GENERALLY, 1 FIRE EXTINGUISHER WITH A MINIMUM RATING OF 2A 10BC SHALL BE INSTALLED PER EVERY 3,000 SQUARE FEET OF FLOOR AREA. THE LOCATION OF THE FIRE EXTINGUISHERS SHALL BE NEAR THE EXIT DOORS AND TRAVEL DISTANCE TO AN EXTINGUISHER SHALL NOT EXCEED 75 FEET. ADDITIONAL SIGNAGE MAY BE NECESSARY TO INDICATE THE FIRE EXTINGUISHER LOCATION.
|
|||||
Miscellaneous Condition | Open | Engineering Division | Prior to Completion | ||
:
Building permit PRFO20240187 cannot be issued until civil construction permit PRCCP20240183 is issued first. [Yianni Charitou @ 02/13/2024 2:33 PM]
The City shall not be held liable for any conflicts that arise between the approved building plans and approved civil construction plans since the building permits were issued prior to civil approval. Ken Cook authorized that this condition be changed from a prior to issuance condition, per normal procedures, to a prior to completion condition in order for work to begin on the building permit while the civil construction permit is under review. [Yianni Charitou @ 02/15/2024 10:51 AM]
|
Reference Number | Status | Type |
---|---|---|
PRFO20231761 | Closed | Foundation Only |
PRFO20240140 | Permit(s) Issued | Foundation Only |
PRCCP20240183 | Permit(s) Issued | Civil Construction Permit |
PRMH20240272 | Permit(s) Issued | Mechanical - COMMERCIAL ONLY |
PRCTI20240275 | Permit(s) Issued | Commercial - Tenant Improvement/Remodel |
PRCTI20240333 | Permit(s) Issued | Commercial - Tenant Improvement/Remodel |
PRCTI20240438 | Permit(s) Issued | Commercial - Tenant Improvement/Remodel |
PRCTI20240560 | Permit(s) Issued | Commercial - Tenant Improvement/Remodel |
PRFO20240573 | Permit(s) Issued | Foundation Only |
PRMH20240593 | Permit(s) Issued | Mechanical - COMMERCIAL ONLY |
PRFS20240598 | Closed | Fire Sprinklers |
PRCNC20240601 | Permit(s) Issued | Commercial - New Construction |
PRFA20240642 | Closed | Fire Alarms |
PRCNC20240647 | Permit(s) Issued | Commercial - New Construction |
PRFN20240667 | Permit(s) Issued | Fence |
PRCTI20240782 | Permit(s) Issued | Commercial - Tenant Improvement/Remodel |
PRCTI20240784 | Permit(s) Issued | Commercial - Tenant Improvement/Remodel |
PRFA20240822 | Closed | Fire Alarms |
PRMH20240831 | Permit(s) Issued | Mechanical - COMMERCIAL ONLY |
PRCTI20240892 | Permit(s) Issued | Commercial - Tenant Improvement/Remodel |
PRFA20241312 | Closed | Fire Alarms |
PRCTI20241387 | Permit(s) Issued | Commercial - Tenant Improvement/Remodel |
PRFA20241456 | Closed | Fire Alarms |
PRFA20241475 | Permit(s) Issued | Fire Alarms |
PRFS20241490 | Closed | Fire Sprinklers |
PRCNC20241741 | Ready for Issuance | Commercial - New Construction |
PRMH20241875 | Permit(s) Issued | Mechanical - COMMERCIAL ONLY |
PRRWF20241913 | Returned for Correction | Retaining Wall |
PRCTI20242004 | Permit(s) Issued | Commercial - Tenant Improvement/Remodel |
PRCTI20250032 | Returned for Correction | Commercial - Tenant Improvement/Remodel |
PRFA20250095 | In Plan Check | Fire Alarms |
PLPRE20230121 | File Closed | Pre-Application |
PLSSP20240018 | File Closed | SEPA Standalone |