CITY OF PUYALLUP PERMITTING PORTAL

Permit Application Status

PRCTI20260575


In order to request inspections, you need to be signed in.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRCTI20260575
Commercial - Tenant Improvement/Remodel
Permit(s) Issued
BENAROYA CAPITAL COMPANY LLC
Alteration/Remodel
Construct interior 2,424 s.f. expansion of existing server room. - CENTERIS, DATA CENTER
04/21/2026
05/20/2026
12/21/2026

Locations

Reviews

Review Type Outcome Est. Completion Date Completed
Fire Review Approved 05/26/2026 05/15/2026
Building Review Approved 05/26/2026 05/15/2026
Planning Review VOID 05/26/2026 05/15/2026
Engineering Traffic Review VOID 05/26/2026 05/15/2026
Engineering Review VOID 05/26/2026 05/12/2026

Fees

Paid Fees Amount Paid Owing Date Paid
Fire Review Fee (Commercial Building) $265.00 $265.00 Paid 05/20/2026
Building Permit Fee $23,858.75 $23,858.75 Paid 05/20/2026
Building Plan Review Fee $15,508.19 $15,508.19 Paid 04/27/2026
WA State Building Code Council Fee (Commercial) $25.00 $25.00 Paid 05/20/2026
Air Handling Unit (Up to 10,000 cfm) Fee $14.10 $14.10 Paid 05/20/2026
Mechanical Duct Work Fee $24.00 $24.00 Paid 05/20/2026
Mechanical Permit Fee $40.00 $40.00 Paid 05/20/2026
Mechanical Plan Review Fee $50.77 $50.77 Paid 04/27/2026
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Comment Building Div Inspection Pending
Shannon King ((253) 840-6684)
Comment Engineering Div Inspection Pending
Footing/Setback Inspection Pending
Shannon King ((253) 840-6684)
Slab/Insulation Inspection Pending
Shannon King ((253) 840-6684)
Roof Sheathing Inspection Pending
Shannon King ((253) 840-6684)
Shear Wall Inspection Pending
Shannon King ((253) 840-6684)
Firewall/Firestop Inspection Pending
Shannon King ((253) 840-6684)
Energy (Insulation) Inspection Pending
Shannon King ((253) 840-6684)
Combination Frame And Rough In Inspection Pending
Shannon King ((253) 840-6684)
Ceiling Grid/T-Bar Inspection Pending
Shannon King ((253) 840-6684)
Exit Lighting Test Inspection Pending
David Drake ((253) 864-4171)
Hydronic Piping Inspection Pending
Shannon King ((253) 840-6684)
Refrigeration Line Test Inspection Pending
Shannon King ((253) 840-6684)
Exhaust Hood Inspection Pending
Shannon King ((253) 840-6684)
Light Test For Grease Duct Inspection Pending
Shannon King ((253) 840-6684)
Exhaust/Vent Fans Inspection Pending
Shannon King ((253) 840-6684)
Medical Gas Inspection Pending
Shannon King ((253) 840-6684)
Fire Or Smoke Damper Inspection Pending
David Drake ((253) 864-4171)
Hydrostatic Test 200Lbs 2Hrs Pending
David Drake ((253) 864-4171)
Emergency Radio Test Review Inspection Pending
David Drake ((253) 864-4171)
Engineering Final Inspection Pending
Fire Final Inspection Pending
David Drake ((253) 864-4171)
Mechanical Final Inspection Pending
Shannon King ((253) 840-6684)
Building Final Inspection Pending
Shannon King ((253) 840-6684)
Foundation/Rebar Inspection Pending
Shannon King ((253) 840-6684)
Wallboard / Drywall Inspection Pending
Shannon King ((253) 840-6684)
Mechanical Rough In Inspection Pending 6/25/2026 6/25/2026
Shannon King ((253) 840-6684)
Frame Inspection Pending 6/25/2026 6/25/2026
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Outstanding
06/16/2026
complete framing details of 3rd floor non rated shaft wall assembly at top track of wall.

Frame Inspection Partial Pass 5/21/2026 5/21/2026 05/21/2026
Shannon King ((253) 840-6684)
Mechanical Rough In Inspection Partial Pass 5/26/2026 5/26/2026 05/26/2026
James LaVergne ((253) 841-5590)
Foundation/Rebar Inspection Partial Pass 5/28/2026 5/28/2026 05/28/2026
Shannon King ((253) 840-6684)
Wallboard / Drywall Inspection Partial Pass 5/28/2026 5/28/2026 05/28/2026
Shannon King ((253) 840-6684)
Wallboard / Drywall Inspection Partial Pass 6/1/2026 6/1/2026 06/01/2026
Shannon King ((253) 840-6684)
Mechanical Rough In Inspection Partial Pass 6/9/2026 6/9/2026 06/09/2026
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Carried Forward
06/09/2026
Chilled water rough in inspection, mez, @ LVL.2 ok at 103 psi (24hr test)

Frame Inspection Failed 6/11/2026 6/11/2026 06/11/2026
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Carried Forward
06/11/2026
complete framing details of 3rd floor non rated shaft wall assembly at top track of wall.

Frame Inspection Not Ready 6/16/2026 6/16/2026 06/16/2026
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Carried Forward
06/16/2026
complete framing details of 3rd floor non rated shaft wall assembly at top track of wall.

Conditions

Condition Status Category
Building Permit Standard Conditions Open Standard Conditions
Building Division
* Final approval by the Building Official is required prior to use or occupancy.* Work shall not proceed until the inspector has approved the stages of construction.* Surface storm water shall be diverted from the building site and shall not drain onto adjacent properties.* I hereby acknowledge that I have read this Permit/Application, that the information given is correct; that I am the owner or the duly authorized agent of the owner; that plans submitted herewith are in compliance with all applicable city, county and state laws and that all construction will proceed in accordance with said laws. This permit shall expire if work is not commenced with 180 days or if the work is suspended for a period of 180 days. Permits expire two years from issuance. * By leaving the contractor information section blank, I hereby certify further that contractors (general or subcontractors) will not be hired to perform any work in association with this permit. I also certify that if I do choose to hire a contractor (general or subcontractor) I will only hire those contractors that are licensed by the State of Washington. If you are a property owner, contractor or permittee and you are paying for someone to perform the work, they must have a valid contractor registration and the person(s) installing plumbing inside a structure must meet the plumbing certification requirements. If you have any questions regarding these regulations, you may contact the Washington State Department of Labor and Industries or you can find more information on-line at: http://www.lni.wa.gov/TradesLicensing/Contractors/HireCon/default.asp
Fire Review Conditions Open Standard Conditions
Provide detailed report from Coffman Engineering's FPE as provided throughout the rest of the project showing all codes, standards, and recommendations have been met.
Possible Contamination Advisory Notice Resolved Standard Conditions
Engineering Division
Interior work only. Contamination notice not applicable.

Related Permit & Planning Applications

Reference Number Status Type
PRFO20231761 Closed Foundation Only
PRFO20240140 Closed Foundation Only
PRCCP20240183 Permit(s) Issued Civil Construction Permit
PRFO20240187 Permit(s) Issued Foundation Only
PRMH20240272 Closed Mechanical - COMMERCIAL ONLY
PRCTI20240275 Closed Commercial - Tenant Improvement/Remodel
PRCTI20240333 Permit(s) Issued Commercial - Tenant Improvement/Remodel
PRCTI20240438 Closed Commercial - Tenant Improvement/Remodel
PRCTI20240560 Closed Commercial - Tenant Improvement/Remodel
PRFO20240573 Closed Foundation Only
PRMH20240593 Closed Mechanical - COMMERCIAL ONLY
PRFS20240598 Closed Fire Sprinklers
PRCNC20240601 Closed Commercial - New Construction
PRFA20240642 Closed Fire Alarms
PRCNC20240647 Closed Commercial - New Construction
PRFN20240667 Closed Fence
PRCTI20240782 Permit(s) Issued Commercial - Tenant Improvement/Remodel
PRCTI20240784 Permit(s) Issued Commercial - Tenant Improvement/Remodel
PRFA20240822 Closed Fire Alarms
PRMH20240831 Closed Mechanical - COMMERCIAL ONLY
PRCTI20240892 Closed Commercial - Tenant Improvement/Remodel
PRFA20241312 Closed Fire Alarms
PRCTI20241387 Permit(s) Issued Commercial - Tenant Improvement/Remodel
PRFA20241456 Closed Fire Alarms
PRFA20241475 Permit(s) Issued Fire Alarms
PRFS20241490 Closed Fire Sprinklers
PRCNC20241741 Permit(s) Issued Commercial - New Construction
PRMH20241875 Closed Mechanical - COMMERCIAL ONLY
PRRWF20241913 Closed Retaining Wall
PRCTI20242004 Permit(s) Issued Commercial - Tenant Improvement/Remodel
PRCTI20250032 Permit(s) Issued Commercial - Tenant Improvement/Remodel
PRFA20250095 Permit(s) Issued Fire Alarms
PRFS20250257 Closed Fire Sprinklers
PRFA20250292 Closed Fire Alarms
PRCTI20250361 Permit(s) Issued Commercial - Tenant Improvement/Remodel
PRFA20250454 Closed Fire Alarms
PRFA20250542 Closed Fire Alarms
PRFA20250621 Closed Fire Alarms
PRFS20250986 Permit(s) Issued Fire Sprinklers
PRFS20251390 Closed Fire Sprinklers
PRFA20251430 Closed Fire Alarms
PRFA20260831 In Plan Check Fire Alarms
PRFS20260843 In Plan Check Fire Sprinklers
PRFA20260863 In Plan Check Fire Alarms
PLPRE20230121 File Closed Pre-Application
PLSSP20240018 File Closed SEPA Standalone
PLBDJ20260066 Complete Application Boundary Line Adjustment

Documents & Images

Date Uploaded File Type Name
04/22/2026 Letter Incomplete Submittal Notice
04/27/2026 Receipt Receipt for transaction:2026-000744
05/15/2026 Form Building Permit Application 27-L2 Server Room Row D Expansion (Flattened)
05/18/2026 Plans ARCH DRWGS (Stamped)
05/18/2026 Plans MECHANICALPLANS (Stamped)
05/18/2026 Plans WALL & DECK STRUCTURAL (Stamped)
05/18/2026 Plans BRACING STRUCTURAL PLANS (Stamped)
05/18/2026 Form LIGHTING REQ'S (Stamped)
05/18/2026 Form MECH COMPLIANCE (Stamped)
05/18/2026 Form LIGHTING COMPLIANCE (Stamped)
05/18/2026 Form MECH REQ'S (Stamped)
05/18/2026 Report BRACING - STRUCT CALCS (Stamped)
05/18/2026 Report INTERIOR FRAMING - STRUCT CALCS (Stamped)
05/20/2026 Letter Permit - Detailed
05/20/2026 Letter Permit Job Card594
05/20/2026 Receipt Receipt for transaction:2026-000933
05/21/2026 Report Inspection Report (Frame Inspection)
05/26/2026 Report Inspection Report (Mechanical Rough In Inspection)
05/28/2026 Report Inspection Report (Foundation/Rebar Inspection)
05/28/2026 Report Inspection Report (Wallboard / Drywall Inspection)
06/01/2026 Report Inspection Report (Wallboard / Drywall Inspection)
06/11/2026 Report Inspection Report (Frame Inspection)


Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.