PRCTI20240784


In order to request inspections, you need to be signed in.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRCTI20240784
Commercial - Tenant Improvement/Remodel
Permit(s) Issued
BCC PUYALLUP LLC
Alteration/Remodel
Interior tenant improvement to construct UPS & Battery Rooms totaling 1,753 sf - CENTERIS SCALE MATRIX UPS & BATTERY ROOM TENANT IMPROVEMENT * REVISION (1) - 10/30/2024 - ADD HYDROGEN DETECTION SYSTEM TO BATTERY ROOM
05/10/2024
11/06/2024
06/01/2025

Locations

Reviews

Review Type Outcome Est. Completion Date Completed
Building Review Approved 11/14/2024 11/05/2024
Building Review Approved 07/02/2024 07/02/2024
Engineering Review Approved 07/02/2024 06/27/2024
Planning Review VOID 07/02/2024 06/25/2024
Fire Review Approved 07/02/2024 06/18/2024
Engineering Traffic Review Approved 07/02/2024 06/17/2024
Building Review Failed 06/18/2024 06/11/2024
Planning Review VOID 06/18/2024 06/11/2024
Engineering Review Approved 06/18/2024 06/10/2024
Fire Review Approved 06/18/2024 05/30/2024
Engineering Traffic Review Approved 06/18/2024 05/30/2024

Fees

Paid Fees Amount Paid Owing Date Paid
Fire Review Fee (Commercial Building) $265.00 $265.00 Paid 07/03/2024
Building Permit Fee $818.75 $818.75 Paid 07/03/2024
Building Plan Review Fee $532.19 $532.19 Paid 05/14/2024
WA State Building Code Council Fee (Commercial) $25.00 $25.00 Paid 07/03/2024
Mechanical Duct Work Fee $19.55 $19.55 Paid 07/03/2024
Mechanical Permit Fee $40.00 $40.00 Paid 07/03/2024
Mechanical Plan Review Fee $38.71 $38.71 Paid 07/03/2024
Resubmittal Fee $180.00 $180.00 Paid 06/14/2024
Resubmittal Fee $180.00 $180.00 Paid 11/06/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Erosion And Sediment Inspection Pending
Comment Engineering Div Inspection Pending
Foundation/Rebar Inspection Pending
Shannon King ((253) 840-6684)
Underfloor Inspection Pending
Shannon King ((253) 840-6684)
Slab/Insulation Inspection Pending
Shannon King ((253) 840-6684)
Block Wall Rebar Inspection Pending
Shannon King ((253) 840-6684)
Shear Wall Inspection Pending
Shannon King ((253) 840-6684)
Firewall/Firestop Inspection Pending
Shannon King ((253) 840-6684)
Ceiling Grid/T-Bar Inspection Pending
Shannon King ((253) 840-6684)
Re-Roof Inspection Pending
Shannon King ((253) 840-6684)
Refrigeration Line Test Inspection Pending
Shannon King ((253) 840-6684)
Exhaust/Vent Fans Inspection Pending
Shannon King ((253) 840-6684)
Hydrostatic Test 200Lbs 2Hrs Pending
David Drake ((253) 864-4171)
Emergency Radio Test Review Inspection Pending
David Drake ((253) 864-4171)
Engineering Final Inspection Pending
Planning Final Inspection Pending
Fire Final Inspection Pending
David Drake ((253) 864-4171)
Building Final Inspection Pending
Shannon King ((253) 840-6684)
Energy (Insulation) Inspection Pending
Shannon King ((253) 840-6684)
Other/Miscellaneous
Outstanding
08/01/2024
THIS WAS DRYWALL INSPECTION FOR SECOND BATTERY ROOM 1.exterior of door wall first layer approved 2.interior ceiling 2nd layer approved

Frame Inspection Pending
Shannon King ((253) 840-6684)
Other/Miscellaneous
Outstanding
08/22/2024
date of inspection 8/21/2024 1.new UPS room existing wall that was reframed approved

Footing/Setback Inspection Pending
Shannon King ((253) 840-6684)
Wallboard / Drywall Inspection Pending
Shannon King ((253) 840-6684)
Other/Miscellaneous
Outstanding
08/23/2024
1:battery room 3rd layer and hat channel on lid ok 2:2nd layer both sides of walls at battery room ok

Mechanical Final Inspection Pending
Shannon King ((253) 840-6684)
Other/Miscellaneous
Outstanding
10/05/2024
date of inspection 10/4/2024 1.cancelled on site by contractor

Mechanical Final Inspection Pending
Shannon King ((253) 840-6684)
Comment Building Div Inspection Pending
Shannon King ((253) 840-6684)
Other/Miscellaneous
Outstanding
12/03/2024
Date of inspection 10/22/2024 1 ; complete framing of opening for fire damper as per install instructions as discussed with contractor.

Wallboard / Drywall Inspection Not Ready 7/23/2024 7/23/2024 07/23/2024
Shannon King ((253) 840-6684)
Frame Inspection Not Ready 7/23/2024 7/23/2024 07/23/2024
Shannon King ((253) 840-6684)
Frame Inspection Not Ready 7/24/2024 7/24/2024 07/24/2024
Shannon King ((253) 840-6684)
Wallboard / Drywall Inspection Partial Pass 7/24/2024 7/24/2024 07/24/2024
Shannon King ((253) 840-6684)
Frame Inspection Partial Pass 7/30/2024 7/30/2024 07/30/2024
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Carried Forward
07/30/2024
inspection of 2nd battery room 1.provide putty packs at electrical boxes 2.ok to cover areas as discussed with contractor

Wallboard / Drywall Inspection Partial Pass 7/31/2024 7/31/2024 08/01/2024
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Carried Forward
08/01/2024
1. putty packs at door wall approved ok to cover 2.exterior other 3 walls first layer approved 3.interior ceiling first layer approved this area is the second battery room

Energy (Insulation) Inspection Partial Pass 8/1/2024 8/1/2024 08/01/2024
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Carried Forward
08/01/2024
THIS WAS DRYWALL INSPECTION FOR SECOND BATTERY ROOM 1.exterior of door wall first layer approved 2.interior ceiling 2nd layer approved

Frame Inspection Not Ready 8/1/2024 8/1/2024 08/01/2024
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Resolved
08/01/2024
inspection of 2nd battery room 1.provide putty packs at electrical boxes 2.ok to cover areas as discussed with contractor

Other/Miscellaneous
Carried Forward
08/01/2024
cancelled on site by contractor

Wallboard / Drywall Inspection Partial Pass 8/2/2024 8/2/2024 08/02/2024
Monty Johnson ((253) 770-3326)
Other/Miscellaneous
Carried Forward
08/02/2024
1. putty packs at door wall approved ok to cover 2.exterior other 3 walls first layer approved 3.interior ceiling first layer approved this area is the second battery room

Other/Miscellaneous
Carried Forward
08/02/2024
1:battery room 3rd layer and hat channel on lid ok 2:2nd layer both sides of walls at battery room ok

Wallboard / Drywall Inspection Not Ready 8/6/2024 8/6/2024 08/07/2024
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Carried Forward
08/07/2024
1:battery room 3rd layer and hat channel on lid ok 2:2nd layer both sides of walls at battery room ok

Other/Miscellaneous
Carried Forward
08/07/2024
1.cancelled on site by contractor

Frame Inspection Not Ready 8/20/2024 8/20/2024 08/20/2024
Shannon King ((253) 840-6684)
Other/Miscellaneous
Resolved
08/20/2024
cancelled on site by contractor

Other/Miscellaneous
Carried Forward
08/20/2024
1; Provide City approved plans or r.f.i. at time of framing inspection for new ups room mechanical penetration of wall.

Frame Inspection Partial Pass 8/21/2024 8/21/2024 08/22/2024
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Resolved
08/22/2024
1; Provide City approved plans or r.f.i. at time of framing inspection for new ups room mechanical penetration of wall.

Other/Miscellaneous
Carried Forward
08/22/2024
date of inspection 8/21/2024 1.new UPS room existing wall that was reframed approved

Footing/Setback Inspection Partial Pass 8/22/2024 8/22/2024 08/22/2024
Shannon King ((253) 840-6684)
Wallboard / Drywall Inspection Not Ready 8/23/2024 8/23/2024 08/23/2024
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
08/23/2024
1:battery room 3rd layer and hat channel on lid ok 2:2nd layer both sides of walls at battery room ok

Other/Miscellaneous
Resolved
08/23/2024
1.cancelled on site by contractor

Comment Building Div Inspection Partial Pass 8/26/2024 8/26/2024 08/27/2024
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Carried Forward
08/27/2024
date of inspection 8/26/2024 1.new steel that was welded on site in 2nd UPS room approved

Mechanical Final Inspection Not Ready 10/4/2024 10/4/2024 10/05/2024
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Carried Forward
10/05/2024
date of inspection 10/4/2024 1.cancelled on site by contractor

Fire Or Smoke Damper Inspection Not Ready 10/17/2024 10/17/2024 10/17/2024
David Drake ((253) 864-4171)
Comment Building Div Inspection Failed 10/22/2024 10/22/2024 10/22/2024
Shannon King ((253) 840-6684)
Other/Miscellaneous
Resolved
10/22/2024
date of inspection 8/26/2024 1.new steel that was welded on site in 2nd UPS room approved

Other/Miscellaneous
Carried Forward
10/22/2024
Date of inspection 10/22/2024 1 ; complete framing of opening for fire damper as per install instructions as discussed with contractor.

Comment Building Div Inspection Failed 10/30/2024 10/30/2024 10/30/2024
Monty Johnson ((253) 770-3326)
Other/Miscellaneous
Carried Forward
10/30/2024
Date of inspection 10/22/2024 1 ; complete framing of opening for fire damper as per install instructions as discussed with contractor.

Other/Miscellaneous
Outstanding
10/30/2024
complete framing around damper as per install instructions

Fire Or Smoke Damper Inspection VOID 12/3/2024 12/3/2024 12/03/2024
David Drake ((253) 864-4171)
Comment Building Div Inspection Not Ready 12/3/2024 12/3/2024 12/03/2024
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
12/03/2024
Date of inspection 10/22/2024 1 ; complete framing of opening for fire damper as per install instructions as discussed with contractor.

Conditions

Condition Status Department Category Expiration Date Due Date
Building Permit Standard Conditions Open Building Division Standard Conditions
: * Final approval by the Building Official is required prior to use or occupancy.* Work shall not proceed until the inspector has approved the stages of construction.* Surface storm water shall be diverted from the building site and shall not drain onto adjacent properties.* I hereby acknowledge that I have read this Permit/Application, that the information given is correct; that I am the owner or the duly authorized agent of the owner; that plans submitted herewith are in compliance with all applicable city, county and state laws and that all construction will proceed in accordance with said laws. This permit shall expire if work is not commenced with 180 days or if the work is suspended for a period of 180 days. Permits expire two years from issuance. * By leaving the contractor information section blank, I hereby certify further that contractors (general or subcontractors) will not be hired to perform any work in association with this permit. I also certify that if I do choose to hire a contractor (general or subcontractor) I will only hire those contractors that are licensed by the State of Washington. If you are a property owner, contractor or permittee and you are paying for someone to perform the work, they must have a valid contractor registration and the person(s) installing plumbing inside a structure must meet the plumbing certification requirements. If you have any questions regarding these regulations, you may contact the Washington State Department of Labor and Industries or you can find more information on-line at: http://www.lni.wa.gov/TradesLicensing/Contractors/HireCon/default.asp
Fire Review Conditions Open Standard Conditions
: • Comply with 2021 IFC and 2021 IBC • Total coverage required in the city of puyallup • L&I Final required prior to Fire Final • Exit lighting test required, contractor to provide light meter • Separate permits required for Fire Alarm and Fire Sprinkler • RTU’S will be required to be tested for shut down with Fire Alarm • Smoke and Fire dampeners will be tested with Fire Alarm. Access doors are required for maintenance and visual inspection. • Fire extinguishers required per code to be installed at time of Fire Final • In existing buildings all required service and maintenance to be completed prior to inspection for the Fire Alarm, and Fire Sprinkler Systems. • All above items to be completed prior to fire final. Fire final required before building final Schedule your inspection online through the city of puyallup online permit system. This is a request for inspection only. A date and time will be selected by Inspector depending on availability. Email morning of inspection between 7am – 8am for scheduled date and time. Fire Inspections are Monday – Thursday there will be no inspections on Fridays. David Drake ddrake@puyallupwa.gov
Contaminated Site Remediation Open Engineering Division Standard Conditions
: The subject property has been classified as a contaminated site by the Tacoma Pierce County Health Department (TPCHD) and must be remediated per Washington Administrative Code Title 173. It is the applicant’s responsibility to coordinate cleanup with TPCHD. Visit https://www.tpchd.org/healthy-places/contaminated-property-cleanup for more information. The applicant shall request a remediation status report from TPCHD by emailing UST@tpchd.org. Provide a copy of the status report to the City.

Related Permit & Planning Applications

Reference Number Status Type
PRFO20231761 Closed Foundation Only
PRFO20240140 Permit(s) Issued Foundation Only
PRCCP20240183 Permit(s) Issued Civil Construction Permit
PRFO20240187 Permit(s) Issued Foundation Only
PRMH20240272 Permit(s) Issued Mechanical - COMMERCIAL ONLY
PRCTI20240275 Permit(s) Issued Commercial - Tenant Improvement/Remodel
PRCTI20240333 Permit(s) Issued Commercial - Tenant Improvement/Remodel
PRCTI20240438 Permit(s) Issued Commercial - Tenant Improvement/Remodel
PRCTI20240560 Permit(s) Issued Commercial - Tenant Improvement/Remodel
PRFO20240573 Permit(s) Issued Foundation Only
PRMH20240593 Permit(s) Issued Mechanical - COMMERCIAL ONLY
PRFS20240598 Closed Fire Sprinklers
PRCNC20240601 Permit(s) Issued Commercial - New Construction
PRFA20240642 Closed Fire Alarms
PRCNC20240647 Permit(s) Issued Commercial - New Construction
PRFN20240667 Permit(s) Issued Fence
PRCTI20240782 Permit(s) Issued Commercial - Tenant Improvement/Remodel
PRFA20240822 Closed Fire Alarms
PRMH20240831 Permit(s) Issued Mechanical - COMMERCIAL ONLY
PRCTI20240892 Permit(s) Issued Commercial - Tenant Improvement/Remodel
PRFA20241312 Closed Fire Alarms
PRCTI20241387 Permit(s) Issued Commercial - Tenant Improvement/Remodel
PRFA20241456 Closed Fire Alarms
PRFA20241475 Permit(s) Issued Fire Alarms
PRFS20241490 Closed Fire Sprinklers
PRCNC20241741 Ready for Issuance Commercial - New Construction
PRMH20241875 Permit(s) Issued Mechanical - COMMERCIAL ONLY
PRRWF20241913 Returned for Correction Retaining Wall
PRCTI20242004 Permit(s) Issued Commercial - Tenant Improvement/Remodel
PRCTI20250032 Returned for Correction Commercial - Tenant Improvement/Remodel
PRFA20250095 In Plan Check Fire Alarms
PLPRE20230121 File Closed Pre-Application
PLSSP20240018 File Closed SEPA Standalone

Documents & Images

Date Uploaded File Type Name
05/14/2024 Receipt Receipt for transaction:2024-001014
05/16/2024 Letter Incomplete Application Notice
06/11/2024 Form Building Permit Application 15 SM UPS Battery Room0 (Flattened)
06/11/2024 Letter Permit Review Correction Letter
06/14/2024 Receipt Receipt for transaction:2024-001265
07/03/2024 Plans CONSTRUCTION PLAN SET - 2024-06-14_Centeris Scale Matrix Battery Room_Permit Revisions 1_Dwgs - RESUB (Stamped)
07/03/2024 Plans CONSTRUCTION PLAN SET - Centeris SM UPS + Battery Room Architectural Drawings-240614 R1 - RESUB (Stamped)
07/03/2024 Plans CONSTRUCTION PLAN SET - Centeris_Scale Matrix_Permit_R1_20240624 - RESUB (Stamped)
07/03/2024 Form ENERGY CODE WORKSHEETS - WSEC MEC Code Requirements List_ SM Battery - RESUB (Stamped)
07/03/2024 Letter Permit - Detailed
07/03/2024 Receipt Receipt for transaction:2024-001393
07/03/2024 Report STRUCTURAL CALCS - RESUB (Stamped)
07/23/2024 Report Inspection Report (Frame Inspection)
07/23/2024 Report Inspection Report (Wallboard / Drywall Inspection)
07/24/2024 Report Inspection Report (Frame Inspection)
07/30/2024 Report Inspection Report (Frame Inspection)
08/01/2024 Report Inspection Report (Energy (Insulation) Inspection)
08/01/2024 Report Inspection Report (Frame Inspection)
08/01/2024 Report Inspection Report (Wallboard / Drywall Inspection)
08/07/2024 Report Inspection Report (Wallboard / Drywall Inspection)
08/21/2024 Report Inspection Report (Frame Inspection)
08/22/2024 Report Inspection Report (Frame Inspection)
08/23/2024 Report Inspection Report (Footing/Setback Inspection)
08/23/2024 Report Inspection Report (Wallboard / Drywall Inspection)
08/27/2024 Report Inspection Report (Comment Building Div Inspection)
10/05/2024 Report Inspection Report (Mechanical Final Inspection)
10/22/2024 Report Inspection Report (Comment Building Div Inspection)
11/06/2024 Letter Permit - Detailed0
11/06/2024 Receipt Receipt for transaction:2024-002314
12/03/2024 Report Inspection Report (Comment Building Div Inspection)