PRMH20240272
Mechanical - COMMERCIAL ONLY
Permit(s) Issued
BCC PUYALLUP LLC
Other
Phase 1 buildout of the existing chilled water plant. Install (4) new RAUs, Install (16) new Evap/Filter Sections, Install (20) OSA Intake Penthouses on Roof, Install (3) new fan walls w/120 exhaust fans. Provide and install an additional 1,200,000 CFM of building exhaust on the 1st floor to match the total supply of RAU CFM. Sheet metal connections between new equipment to existing system. - CENTERIS VOLTAGE PARK
02/22/2024
03/18/2024
11/08/2024

Locations

Reviews

Review Type Outcome Est. Completion Date Completed
Engineering Review Approved 03/07/2024 03/14/2024
Mechanical Review Approved 03/07/2024 03/07/2024

Fees

Paid Fees Amount Paid Owing Date Paid
Air Handling Unit (Over 10,000 cfm) Fee $95.68 $95.68 Paid 03/18/2024
Unclassified Appliance or Equipment Fee $549.90 $549.90 Paid 03/18/2024
Mechanical Permit Fee $40.00 $40.00 Paid 03/18/2024
Mechanical Plan Review Fee $445.63 $445.63 Paid 02/22/2024
Water System Development Charge $889.75 $889.75 Paid 03/18/2024
$0.00
Sewer System Development Charge $3,461.60 $3,461.60 Paid 03/18/2024
$0.00
Inspection Fee - Outside Of Business Hours $540.00 $540.00 Paid 05/09/2024
Inspection Fee - Outside Of Business Hours $540.00 $540.00 Paid 05/09/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Gas Test Inspection Pending
Shannon King ((253) 840-6684)
Mechanical Final Inspection Pending
Shannon King ((253) 840-6684)
Firewall/Firestop Inspection Pending
Shannon King ((253) 840-6684)
Other/Miscellaneous
Outstanding
04/17/2024
1. this inspection was performed on 4/16/2024 2.mineral wool at flutes approved

Mechanical Rough In Inspection Pending
Shannon King ((253) 840-6684)
Wallboard / Drywall Inspection Pending
Shannon King ((253) 840-6684)
Frame Inspection Pending
Shannon King ((253) 840-6684)
Wallboard / Drywall Inspection Pending
Shannon King ((253) 840-6684)
Comment Building Div Inspection Failed 3/20/2024 3/20/2024 03/20/2024
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
03/20/2024
1 ; inspection of new floor opening at Data Hall per sheet S4.0 of City approved plans . 2 ; provide special inspection approval report for welding of beam, and bolting prior to frame approval.

Comment Building Div Inspection Not Ready 4/2/2024 4/2/2024 04/02/2024
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
04/02/2024
1 ; inspection of new floor opening at Data Hall per sheet S4.0 of City approved plans . 2 ; provide special inspection approval report for welding of beam, and bolting prior to frame approval.

Firewall/Firestop Inspection Partial Pass 4/17/2024 04/17/2024
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Carried Forward
04/17/2024
1. this inspection was performed on 4/16/2024 2.mineral wool at flutes approved

Mechanical Rough In Inspection Partial Pass 4/23/2024 4/23/2024 04/23/2024
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
04/23/2024
1 ; provide special inspection report for anchor bolt install. 2 ; provide engineers approval of welding at north mechanical wall at opening 1&2. ( ok to insulate)

Mechanical Rough In Inspection Partial Pass 4/29/2024 4/29/2024 04/29/2024
Shannon King ((253) 840-6684)
Other/Miscellaneous
Resolved
04/29/2024
1 ; provide special inspection report for anchor bolt install. 2 ; provide engineers approval of welding at north mechanical wall at opening 1&2. ( ok to insulate)

Wallboard / Drywall Inspection Partial Pass 5/10/2024 5/10/2024 05/10/2024
Shannon King ((253) 840-6684)
Frame Inspection Partial Pass 5/10/2024 5/10/2024 05/10/2024
Shannon King ((253) 840-6684)
Wallboard / Drywall Inspection Partial Pass 5/11/2024 5/11/2024 05/12/2024
Shannon King ((253) 840-6684)

Conditions

Condition Status Department Category Expiration Date Due Date
Building Permit Standard Conditions Open Building Division Standard Conditions
: * Final approval by the Building Official is required prior to use or occupancy.* Work shall not proceed until the inspector has approved the stages of construction.* Surface storm water shall be diverted from the building site and shall not drain onto adjacent properties.* I hereby acknowledge that I have read this Permit/Application, that the information given is correct; that I am the owner or the duly authorized agent of the owner; that plans submitted herewith are in compliance with all applicable city, county and state laws and that all construction will proceed in accordance with said laws. This permit shall expire if work is not commenced with 180 days or if the work is suspended for a period of 180 days. Permits expire two years from issuance. * By leaving the contractor information section blank, I hereby certify further that contractors (general or subcontractors) will not be hired to perform any work in association with this permit. I also certify that if I do choose to hire a contractor (general or subcontractor) I will only hire those contractors that are licensed by the State of Washington. If you are a property owner, contractor or permittee and you are paying for someone to perform the work, they must have a valid contractor registration and the person(s) installing plumbing inside a structure must meet the plumbing certification requirements. If you have any questions regarding these regulations, you may contact the Washington State Department of Labor and Industries or you can find more information on-line at: http://www.lni.wa.gov/TradesLicensing/Contractors/HireCon/default.asp
Contaminated Site Remediation Open Engineering Division Standard Conditions
: The subject property has been classified as a contaminated site by the Tacoma Pierce County Health Department (TPCHD) and must be remediated per Washington Administrative Code Title 173. It is the applicant’s responsibility to coordinate cleanup with TPCHD. Visit https://www.tpchd.org/healthy-places/contaminated-property-cleanup for more information. The applicant shall request a remediation status report from TPCHD by emailing UST@tpchd.org. Provide a copy of the status report to the City.
Miscellaneous Condition Open Engineering Division Standard Conditions
: According to UPC Table 702.2(1), the proposed 4" trap serving the new 10,000 gallon tank is equivalent to 8 drainage fixture units. Each sewer fixture unit is currently $432.70 above the first 15 units. $3,461.60 sewer system development charges were assessed for the tank that supplies the new Recirculated Air Units. [Yianni Charitou @ 03/06/2024 4:00 PM] According to footnote 2 of UPC Table 610.3, appliances appurtenances, or fixtures not referenced in this table shall be permitted to be sized by reference to fixtures having similar flow rate and frequency of use. For this project, the proposed 3" branch supplying the new 10,000 gallon tank is sized like a private hose bibb which equals 2.5 water supply fixture units. Each water supply fixture unit is currently $355.90 above the first 15 units. $889.75 water system development charges were assessed for the tank that supplies the new Recirculated Air Units. [Yianni Charitou @ 03/06/2024 4:07 PM]
Miscellaneous Condition Open Engineering Division Prior to Occupancy
: The applicant shall contact the Puyallup Water Pollution Control Plant by calling 253-841-5511 to apply for a pre-treatment/discharge permit which should include a discharge plan for potential pollutants. Written authorization to proceed with the installation, connection, and use of the proposed 10,000 gallon water tank must be obtained from the Puyallup Water Pollution Control Plant prior to resolving this condition. [Yianni Charitou @ 03/07/2024 9:55 AM]

Related Permit & Planning Applications

Reference Number Status Type
PRFO20231761 Permit(s) Issued Foundation Only
PRFO20240140 Permit(s) Issued Foundation Only
PRCCP20240183 In Plan Check Civil Construction Permit
PRFO20240187 Permit(s) Issued Foundation Only
PRCTI20240275 Permit(s) Issued Commercial - Tenant Improvement/Remodel
PRCTI20240333 Permit(s) Issued Commercial - Tenant Improvement/Remodel
PRCTI20240438 Permit(s) Issued Commercial - Tenant Improvement/Remodel
PRCTI20240560 Ready for Issuance Commercial - Tenant Improvement/Remodel
PRFO20240573 In Plan Check Foundation Only
PRMH20240593 Permit(s) Issued Mechanical - COMMERCIAL ONLY
PRFS20240598 Permit(s) Issued Fire Sprinklers
PRCTI20240601 In Plan Check Commercial - Tenant Improvement/Remodel
PRFA20240642 Permit(s) Issued Fire Alarms
PRCNC20240647 In Plan Check Commercial - New Construction
PRFN20240667 Returned for Correction Fence
PLPRE20230121 File Closed Pre-Application
PLSSP20240018 File Closed SEPA Standalone

Documents & Images


Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.