| Review Type |
Outcome |
Est. Completion Date |
Completed |
|
Building Review
|
Approved
|
02/28/2025
|
02/06/2025
|
|
|
|
|
Fire Review
|
Approved
|
10/29/2024
|
10/02/2024
|
|
|
|
|
Planning Review
|
Approved
|
10/29/2024
|
10/02/2024
|
|
|
|
|
Building Review
|
Approved
|
10/29/2024
|
10/02/2024
|
|
|
|
|
|
See Document Markup
Please review the Phase 2 EV charging requirements. 13 EV charging stations are required per the calculations, yet only 12 are noted as provided. [CONSTRUCTION PLAN SET - RESUB, sheet AG1.2]
|
|
|
See Document Markup
Please show and note the maximum exit access travel distances for each unit to confirm they comply with Table 1006.2.1 in the 2018 Washington State Building Code. [CONSTRUCTION PLAN SET - RESUB, sheet A1.0]
|
|
|
See Document Markup
Please show and note the maximum exit access travel distances for each unit to confirm they comply with Table 1006.2.1 in the 2018 Washington State Building Code. [CONSTRUCTION PLAN SET - RESUB, sheet A1.1]
|
|
|
See Document Markup
Please show and note the maximum exit access travel distances for each unit to confirm they comply with Table 1006.2.1 in the 2018 Washington State Building Code. [CONSTRUCTION PLAN SET - RESUB, sheet A1.2]
|
|
|
See Document Markup
Please relocate this turning radius so it isn't shown intersecting the vanity. [CONSTRUCTION PLAN SET - RESUB, sheet A1.4]
|
|
|
See Document Markup
Please relocate this turning radius so it isn't shown intersecting the vanity. [CONSTRUCTION PLAN SET - RESUB, sheet A1.5]
|
|
|
See Document Markup
Please show the location of the roof access hatch on the floor plan. [CONSTRUCTION PLAN SET - RESUB, sheet A1.8]
|
|
|
See Document Markup
All details on this sheet: the sheet call-out for the rated wall assemblies are incorrect. Please revise the notes to AG1.4. [CONSTRUCTION PLAN SET - RESUB, sheet A6.1]
|
|
|
See Document Markup
This note references the TMC (Tacoma Municipal Code assumed). Please revise this note to conform to the City of Puyallup (if applicable). [CONSTRUCTION PLAN SET - RESUB, sheet A6.1]
|
|
|
See Document Markup
This note references the TMC (Tacoma Municipal Code assumed). Please revise this note to conform to the City of Puyallup (if applicable). [CONSTRUCTION PLAN SET - RESUB, sheet A6.3]
|
|
|
See Document Markup
ORIGINAL COMMENT: Please confirm the drag load at this girder.
.
REVISED COMMENT: I apologize, the original review comment was not clear in it's intention. The drag girder load noted near gridline 3 appears to be a typo (3,00 rather than 3,000). Please have the engineer of record confirm. [CONSTRUCTION PLAN SET - Bldg B, sheet S3.4]
|
|
|
See Document Markup
The energy credits shown on sheet M0.2 doesn't match the credits noted in the provided WSEC Credit Worksheet or the credits noted on sheet AG1.2. Please ensure mechanical system complies with the energy credits chosen. [CONSTRUCTION PLAN SET - RESUB, sheet M0.2]
|
|
|
See Document Markup
Please revise the table to conform to the 2018 IMC. [CONSTRUCTION PLAN SET - RESUB, sheet M0.2]
|
|
|
See Document Markup
Please revise this code reference to the 2018 WSEC. [CONSTRUCTION PLAN SET - RESUB, sheet P0.01]
|
|
|
See Document Markup
Please revise this code reference to the 2018 WSEC. [CONSTRUCTION PLAN SET - RESUB, sheet P0.01]
|
|
|
See Document Markup
Please revise this code reference to the 2018 WSEC. [CONSTRUCTION PLAN SET - RESUB, sheet P0.01]
|
|
|
See Document Markup
Please revise this code reference to the 2018 WSEC. [CONSTRUCTION PLAN SET - RESUB, sheet P0.01]
|
|
|
See Document Markup
Please revise this code reference to the 2018 WSEC. [CONSTRUCTION PLAN SET - RESUB, sheet P4.01]
|
|
|
See Document Markup
A smoke alarm / carbon monoxide detector is required outside, but within the immediate vicinity of the (plan view) right bedroom. [CONSTRUCTION PLAN SET - RESUB, sheet E5.01]
|
|
|
See Document Markup
A smoke alarm / carbon monoxide detector is required outside, but within the immediate vicinity of the (plan view) right bedroom. Take care to place the alarm no closer than 3ft from the bathroom opening. [CONSTRUCTION PLAN SET - RESUB, sheet E5.01]
|
|
Engineering Review
|
Approved
|
10/29/2024
|
10/02/2024
|
|
|
|
|
Engineering Traffic Review
|
VOID
|
10/29/2024
|
10/01/2024
|
|
|
|
|
Planning Review
|
Failed
|
09/09/2024
|
09/18/2024
|
|
|
|
|
|
Add Submittal Item: Lot Combo
Additional Submittal Item Required: Lot Combination Permit Application required. Application form can be downloaded from the City website at https://www.cityofpuyallup.org/DocumentCenter/View/11646/Lot-Combination-Application
|
|
Engineering Review
|
Approved
|
09/09/2024
|
09/11/2024
|
|
|
|
|
Building Review
|
Failed
|
09/09/2024
|
09/05/2024
|
|
|
|
|
|
See Document Markup
This note references the 2015 IBC. [CONSTRUCTION PLAN SET - Bldg B, sheet AG1.1]
|
|
|
See Document Markup
There are several notes that reference the 2015 IBC. Please revise these notes so they conform to the 2018 Washington State Codes. [CONSTRUCTION PLAN SET - Bldg B, sheet AG1.1]
|
|
|
See Document Markup
Please ensure the interior space is throughly dimensioned. Typical all plan sheets. [CONSTRUCTION PLAN SET - Bldg B]
|
|
|
See Document Markup
Please verify that the interior dimensions of the office complies with section 1207.1 of the 2018 Washington State Building Code. Typical at similar. [CONSTRUCTION PLAN SET - Bldg B]
|
|
|
See Document Markup
Section 3 is partially cut off. [CONSTRUCTION PLAN SET - Bldg B, sheet A3.1]
|
|
|
See Document Markup
Section 6 is partially cut off. [CONSTRUCTION PLAN SET - Bldg B, sheet A3.1]
|
|
|
See Document Markup
Section 7 is partially cut off. [CONSTRUCTION PLAN SET - Bldg B, sheet A3.2]
|
|
|
See Document Markup
Section 8 is partially cut off. [CONSTRUCTION PLAN SET - Bldg B, sheet A3.2]
|
|
|
See Document Markup
Section 8 is partially cut off. [CONSTRUCTION PLAN SET - Bldg B, sheet A3.2]
|
|
|
See Document Markup
Sections 9 and 10 are partially cut off. [CONSTRUCTION PLAN SET - Bldg B, sheet A3.3]
|
|
|
See Document Markup
Please provide these reference sections on the plan set. [CONSTRUCTION PLAN SET - Bldg B, sheet A5.0]
|
|
|
See Document Markup
Please fix these details. [CONSTRUCTION PLAN SET - Bldg B, sheet A5.0]
|
|
|
See Document Markup
Please fix these details. [CONSTRUCTION PLAN SET - Bldg B, sheet A5.1]
|
|
|
See Document Markup
Please fix these details. [CONSTRUCTION PLAN SET - Bldg B, sheet A5.1]
|
|
|
See Document Markup
Please fix these details. [CONSTRUCTION PLAN SET - Bldg B, sheet A5.2]
|
|
|
See Document Markup
Please reference this sheet and the relevant detail(s) on the plan set. [CONSTRUCTION PLAN SET - Bldg B, sheet A6.9]
|
|
|
See Document Markup
Please provide the geotechnical report from Krazan & Asspcoates that supports the 2,000psf allowable soil bearing capacity. [CONSTRUCTION PLAN SET - Bldg B, sheet S1.0]
|
|
|
See Document Markup
Shear wall plans are on sheet S3.6, S3.7, an S3.8. [CONSTRUCTION PLAN SET - Bldg B, sheet S3.1]
|
|
|
See Document Markup
Please confirm the drag load at this girder. [CONSTRUCTION PLAN SET - Bldg B, sheet S3.4]
|
|
|
See Document Markup
Please revise this sheet and associates notes and sheets to conform to the 2018 Washington State Codes. [CONSTRUCTION PLAN SET - Bldg B, sheet P0.01]
|
|
|
See Document Markup
Please revise this sheet and associates notes and sheets to conform to the 2018 Washington State Codes. [CONSTRUCTION PLAN SET - Bldg B, sheet P0.03]
|
|
|
See Document Markup
Sheet P7.00 was not included in the plan set. [CONSTRUCTION PLAN SET - Bldg B, sheet P0.03]
|
|
|
See Document Markup
Please review the Phase 2 EV charging requirements. 13 EV charging stations are required per the calculations, yet only 12 are noted as provided. [CONSTRUCTION PLAN SET - RESUB, sheet AG1.2]
|
|
|
See Document Markup
Please relocate this turning radius so it isn't shown intersecting the vanity. [CONSTRUCTION PLAN SET - RESUB, sheet A1.4]
|
|
|
See Document Markup
Please relocate this turning radius so it isn't shown intersecting the vanity. [CONSTRUCTION PLAN SET - RESUB, sheet A1.5]
|
|
|
See Document Markup
Please show the location of the roof access hatch on the floor plan. [CONSTRUCTION PLAN SET - RESUB, sheet A1.8]
|
|
|
See Document Markup
All details on this sheet: the sheet call-out for the rated wall assemblies are incorrect. Please revise the notes to AG1.4. [CONSTRUCTION PLAN SET - RESUB, sheet A6.1]
|
|
|
See Document Markup
This note references the TMC (Tacoma Municipal Code assumed). Please revise this note to conform to the City of Puyallup (if applicable). [CONSTRUCTION PLAN SET - RESUB, sheet A6.1]
|
|
|
See Document Markup
This note references the TMC (Tacoma Municipal Code assumed). Please revise this note to conform to the City of Puyallup (if applicable). [CONSTRUCTION PLAN SET - RESUB, sheet A6.3]
|
|
|
See Document Markup
ORIGINAL COMMENT: Please confirm the drag load at this girder.
.
REVISED COMMENT: I apologize, the original review comment was not clear in it's intention. The drag girder load noted near gridline 3 appears to be a typo (3,00 rather than 3,000). Please have the engineer of record confirm. [CONSTRUCTION PLAN SET - Bldg B, sheet S3.4]
|
|
|
See Document Markup
The energy credits shown on sheet M0.2 doesn't match the credits noted in the provided WSEC Credit Worksheet or the credits noted on sheet AG1.2. Please ensure mechanical system complies with the energy credits chosen. [CONSTRUCTION PLAN SET - RESUB, sheet M0.2]
|
|
|
See Document Markup
Please revise this code reference to the 2018 WSEC. [CONSTRUCTION PLAN SET - RESUB, sheet P0.01]
|
|
|
See Document Markup
Please revise this code reference to the 2018 WSEC. [CONSTRUCTION PLAN SET - RESUB, sheet P0.01]
|
|
|
See Document Markup
Please revise this code reference to the 2018 WSEC. [CONSTRUCTION PLAN SET - RESUB, sheet P0.01]
|
|
|
See Document Markup
Please revise this code reference to the 2018 WSEC. [CONSTRUCTION PLAN SET - RESUB, sheet P0.01]
|
|
|
See Document Markup
Please revise this code reference to the 2018 WSEC. [CONSTRUCTION PLAN SET - RESUB, sheet P4.01]
|
|
|
See Document Markup
A smoke alarm / carbon monoxide detector is required outside, but within the immediate vicinity of the (plan view) right bedroom. [CONSTRUCTION PLAN SET - RESUB, sheet E5.01]
|
|
|
See Document Markup
A smoke alarm / carbon monoxide detector is required outside, but within the immediate vicinity of the (plan view) right bedroom. Take care to place the alarm no closer than 3ft from the bathroom opening. [CONSTRUCTION PLAN SET - RESUB, sheet E5.01]
|
|
|
See Document Markup
Please show and note the maximum exit access travel distances for each unit to confirm they comply with Table 1006.2.1 in the 2018 Washington State Building Code. [CONSTRUCTION PLAN SET - RESUB, sheet A1.0]
|
|
|
See Document Markup
Please show and note the maximum exit access travel distances for each unit to confirm they comply with Table 1006.2.1 in the 2018 Washington State Building Code. [CONSTRUCTION PLAN SET - RESUB, sheet A1.1]
|
|
|
See Document Markup
Please show and note the maximum exit access travel distances for each unit to confirm they comply with Table 1006.2.1 in the 2018 Washington State Building Code. [CONSTRUCTION PLAN SET - RESUB, sheet A1.2]
|
|
|
See Document Markup
Please revise the table to conform to the 2018 IMC. [CONSTRUCTION PLAN SET - RESUB, sheet M0.2]
|
|
Fire Review
|
Failed
|
09/09/2024
|
09/04/2024
|
|
|
|
|
|
Other/Miscellaneous
Previous corrections not addressed in correction letter.
|
|
|
Other/Miscellaneous
1. Riser room is required to be on its own dedicated power and not tied into a tenant.
2. I do not see notes on the riser room? Provide an adequate heat source for the riser and the FACP. The FACP will need heat to keep the electronics from condensation.
|
|
Engineering Traffic Review
|
Approved
|
09/09/2024
|
08/30/2024
|
|
|
|
|
Building Review
|
Failed
|
05/15/2024
|
05/14/2024
|
|
|
|
|
|
Other/Miscellaneous
An engineered roof truss layout and calculations will be required prior to issuance to verify engineered loads shown on the plan set are accounted for in the truss design.
|
|
|
See Document Markup
This note references the 2015 IBC. [CONSTRUCTION PLAN SET - Bldg B, sheet AG1.1]
|
|
|
See Document Markup
There are several notes that reference the 2015 IBC. Please revise these notes so they conform to the 2018 Washington State Codes. [CONSTRUCTION PLAN SET - Bldg B, sheet AG1.1]
|
|
|
See Document Markup
Section 3 is partially cut off. [CONSTRUCTION PLAN SET - Bldg B, sheet A3.1]
|
|
|
See Document Markup
Section 6 is partially cut off. [CONSTRUCTION PLAN SET - Bldg B, sheet A3.1]
|
|
|
See Document Markup
Section 7 is partially cut off. [CONSTRUCTION PLAN SET - Bldg B, sheet A3.2]
|
|
|
See Document Markup
Section 8 is partially cut off. [CONSTRUCTION PLAN SET - Bldg B, sheet A3.2]
|
|
|
See Document Markup
Section 8 is partially cut off. [CONSTRUCTION PLAN SET - Bldg B, sheet A3.2]
|
|
|
See Document Markup
Please provide these reference sections on the plan set. [CONSTRUCTION PLAN SET - Bldg B, sheet A5.0]
|
|
|
See Document Markup
Please fix these details. [CONSTRUCTION PLAN SET - Bldg B, sheet A5.0]
|
|
|
See Document Markup
Please fix these details. [CONSTRUCTION PLAN SET - Bldg B, sheet A5.1]
|
|
|
See Document Markup
Please fix these details. [CONSTRUCTION PLAN SET - Bldg B, sheet A5.1]
|
|
|
See Document Markup
Please fix these details. [CONSTRUCTION PLAN SET - Bldg B, sheet A5.2]
|
|
|
See Document Markup
Please reference this sheet and the relevant detail(s) on the plan set. [CONSTRUCTION PLAN SET - Bldg B, sheet A6.9]
|
|
|
See Document Markup
Please provide the geotechnical report from Krazan & Asspcoates that supports the 2,000psf allowable soil bearing capacity. [CONSTRUCTION PLAN SET - Bldg B, sheet S1.0]
|
|
|
See Document Markup
Shear wall plans are on sheet S3.6, S3.7, an S3.8. [CONSTRUCTION PLAN SET - Bldg B, sheet S3.1]
|
|
|
See Document Markup
Please revise this sheet and associates notes and sheets to conform to the 2018 Washington State Codes. [CONSTRUCTION PLAN SET - Bldg B, sheet P0.01]
|
|
|
See Document Markup
Sections 9 and 10 are partially cut off. [CONSTRUCTION PLAN SET - Bldg B, sheet A3.3]
|
|
|
See Document Markup
Please confirm the drag load at this girder. [CONSTRUCTION PLAN SET - Bldg B, sheet S3.4]
|
|
|
See Document Markup
Please revise this sheet and associates notes and sheets to conform to the 2018 Washington State Codes. [CONSTRUCTION PLAN SET - Bldg B, sheet P0.03]
|
|
|
See Document Markup
Please ensure the interior space is throughly dimensioned. Typical all plan sheets. [CONSTRUCTION PLAN SET - Bldg B]
|
|
|
See Document Markup
Please verify that the interior dimensions of the office complies with section 1207.1 of the 2018 Washington State Building Code. Typical at similar. [CONSTRUCTION PLAN SET - Bldg B]
|
|
|
See Document Markup
Sheet P7.00 was not included in the plan set. [CONSTRUCTION PLAN SET - Bldg B, sheet P0.03]
|
|
Engineering Traffic Review
|
Approved
|
05/15/2024
|
05/14/2024
|
|
|
|
|
Fire Review
|
Failed
|
05/15/2024
|
05/09/2024
|
|
|
|
|
|
Other/Miscellaneous
1. Riser room is required to be on its own dedicated power and not tied into a tenant.
2. I do not see notes on the riser room? Provide an adequate heat source for the riser and the FACP. The FACP will need heat to keep the electronics from condensation.
|
|
Engineering Review
|
Approved
|
05/15/2024
|
04/04/2024
|
|
|
|
|
|
See Document Markup
The applicant is responsible to show onsite private utilities services for each building on a site plan. This includes sewer or septic, storm and water. [Site Plan Sheet 1 of ]
|
|
Planning Review
|
Failed
|
05/15/2024
|
04/04/2024
|
|
|
|
|
|
Add Submittal Item: Lot Combo
Additional Submittal Item Required: Lot Combination Permit Application required. Application form can be downloaded from the City website at https://www.cityofpuyallup.org/DocumentCenter/View/11646/Lot-Combination-Application
|